More Troubleshooting Tips; Brine Solution Not Being Sucked In During Regeneration; System Not Backwashing Adequately - Clean Water Systems Fleck 5600 Softener Installation & Start?Up Manual

Table of Contents

Advertisement

Control cycles continuously 
Drain flows continuously 
More Troubleshooting Tips 
Brine Solution Not Being Sucked In During Regeneration 
Most problems occur when the Fleck 5600 is not drawing in the brine.  Make sure the injector is drawing in 
the brine: 
1. Remove the brine tank tubing where it enters the Fleck 5600 control valve.   
2. Press the Extra Cycle button and hold for several seconds until a backwash is started.   After the 
display stops blinking and it is in a backwash cycle, press the Extra Cycle button again, and it will 
advance to the next cycle, which is the Brine Cycle, where it is supposed to suck in the brine solution. 
3. If it is sucking strongly, check the brine tank float inside the brine well and make sure there are no 
rubber bands around it, and that is free of obstructions.  In some cases it may need to be replaced or 
cleaned, if there is suction at the control valve, but no brine is being drawn in. 
4. If there is NO suction at the control valve port where you removed the brine line tubing, then the 
injector should be cleaned.   
5. If the injector has been cleaned and there is still no suction check to make sure there is obstruction in 
the backwash line;  that the backwash line does not go up and over the softener more than several feet 
(which causes pressure loss and the injector not to work correctly); finally check to make sure there is 
enough pressure.  If possible increase your water pressure to softener from your well pump and see if a 
slightly increased pressure makes the injector work.  We recommend a minimum 30 PSI but it does work 
better if there is 40 to 50 minimum PSI. 
System Not Backwashing Adequately 
The other second main problem that may occur is if you do not have enough backwash flow rate to properly 
clean the water softener.  You can verify the backwash flow rate by running the drain line into a bucket and 
timing it when the Fleck 5600 is in Cycle 1 or backwash.  A 1.0 or 1.5 cubic foot system should have 5 gallons 
per minute and a 2.5 cubic foot system should have 10 gallons per minute of backwash. 
Page 15 
Fleck 5600 Softener Installation & Startup Guide 
Misadjusted, broken, or 
shorted switch 
Valve is not 
programming correctly. 
Foreign material in 
control. 
Internal control leak.
www.cleanwaterstore.com 
Determine if switch or timer is faulty and 
replace it, or replace complete power head. 
Check timer program and positioning of 
control. Replace power head assembly if not 
positioning properly. 
Remove power head assembly and inspect 
bore. Remove foreign material 
and check control in various regeneration 
positions 
Replace seals and piston assembly.
Rev 031714 

Advertisement

Table of Contents
loading

Table of Contents