Sinclair ASGE-09AIN WK Service Manual page 44

New uni dc inverter series outdoor units asge-xxain wk indoor units-floor-ceiling, cassette, duct type
Table of Contents

Advertisement

control information to realize control and monitor of the unit.
(2). Function instructions:
In order to achieve this function, set the address mode and address through wired controller. Please refer
to Point 3 for the setting method. You must set the address mode into long-distance control address mode.
The address mode is defaulted to be connecting to centralized controller mode and the defaulted address
is 1.
(3). Setting method:
1). Firstly, set the address mode of wired controller into centralized controller address mode. The setting
method is:
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the debugging
Centralized controller address mode (LCD displays 00)
Long-distance control address mode (LCD displays 01)
Choose the second selection and then press Enter/Cancel button to save and exit setting. Now, the
address of wired controller is set to match the address of long-distance control. The unit will memorize this
setting status. The setting value will be memorized after power failure. The detailed setting is as shown in the
Figure below:
2). Address setting of each unit: when the address mode is set to be long-distance control address mode.
The address setting value range is 01~255. The setting method is:
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
power failure. The detailed setting is as shown in the Figure below:
Figure 2-7-10
38