2.4 IPM, PFC Testing Method
2.4.1 Method of Testing IPM Module
(1). Preparation before test: prepare a universal meter and turn to its diode option, and then remove the
wires U, V, W of the compressor after it is powered off for one minute.
(2). Testing Steps
Step 1: put the black probe on the place P and the red one on the wiring terminal U, V, W respectively as
Step 2: put the red probe on the place N and the black one on the wiring terminal U, V, W respectively as
(3). If the measured voltages between UP, VP, WP, NU, NV, NV are all among 0.3V-0.7V, then it indicates
the IPM module is normal; If any measured valve is 0, it indicates the IPM is damaged.