armed, and HIGH when any enabled partition is disarmed. The remaining triggers are
normally LOW and go HIGH when the corresponding condition occurs in at least one enabled
partition. The fire and burglary/audible panic alarm triggers remain HIGH until a [User
Code] + [OFF] is entered in all enabled partitions that display these conditions. The silent
panic/duress trigger works the same way, except that it is momentary when initiated by
duress. The fire supervisory and trouble triggers remain HIGH until the underlying faults
are corrected and the [User Code] + [OFF] is entered in all enabled partition(s) that
display these conditions.
When a Long Range Radio is installed, configure the sense select for zones 1 and 2 in the
Long Range Radio to activate on +5V (positive trigger). This is necessary to prevent false
alarms from occurring. Refer to the installation instructions provided with your radio for
instructions on setting the zone 1 and 2 levels.
Figures 12-5a, b, and c show how to make connections to the 7720, 7720ULF, and 7920SE
Long Range Radios.
4142TR
CABLE
4142TR
CABLE
WIRE
COLORS
12–6
7720 WIRING DIAGRAM
J2 CONNECTOR
1
2
3
4
5
6
7
NOTES:
• MOUNT THE 7720 WITHIN 3 FEET OF THE C-COM. RUN WIRING FROM C-COM TO 7720 IN CONDUIT.

Figure 12-5a: Connections to 7720 Long Range Radio

8
9
7720 RADIO
(USE 7720 ULF INSTEAD
FOR COMMERCIAL FIRE
INSTALLATIONS)
RADIO FAULT (PROGRAM FOR SHORT ON FAULT)
GROUND
FIRE ALARM
BURG/AUDIBLE PANIC ALARM
TROUBLE (ZONE TROUBLE, TELCO FAULT, ETC.)
SILENT PANIC/DURESS ALARM
SEE 7720 INSTRUCTIONS FOR
MORE DETAILED INSTALLATION
INFORMATION
1
2
3
4
5
6
7
8
FAULT
9
10
11