ADEMCO Vista-32FB Programming Manual
ADEMCO Vista-32FB Programming Manual

ADEMCO Vista-32FB Programming Manual

Commercial fire and burglary partitioned security system with scheduling

Advertisement

9
,
6
7
$



)
%
9
,
6
7
$



)
%
&RPPHUFLDO)LUHDQG%XUJODU\
3DUWLWLRQHG6HFXULW\6\VWHP
ZLWK6FKHGXOLQJ
3URJUDPPLQJ*XLGH
FIRE
FIRE
PULL
®
K3840V1 9/00
www.PDF-Zoo.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Vista-32FB and is the answer not in the manual?

Questions and answers

Summary of Contents for ADEMCO Vista-32FB

  • Page 1 &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 3URJUDPPLQJ*XLGH FIRE FIRE PULL ® K3840V1 9/00 www.PDF-Zoo.com...
  • Page 2: Table Of Contents

    You must enter the number of partitions you are using in data field 2*00 to set the system for multiple partitions. Use the VISTA-32FB SINGLE PARTITION and the PARTITION-SPECIFIC PROGRAM FORMS when programming the system for multiple partitions. Follow the steps outlined in RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.
  • Page 3: Recommended Programming Procedure

    12. Define user access codes. Refer to User Access Codes section in the VISTA-32FB Installation and Setup Guide to program authority level, O/C reporting option, partition assignments, and wireless key assignments for each user.
  • Page 4: Program Field Categories

    Program Field Categories In the following pages, the programming fields have been arranged by category. Use this index to cross reference the numerical ordered fields on the programming form. Field Group Field Group Field Group System-Wide Communications 1*56 System-Wide System-Wide Communications 1*57 System-Wide...
  • Page 5: Vista 32Fb Programming Form

    VISTA 32FB Programming Form Some fields are programmed for each partition (shown as shaded fields). If Programming a Multiple Partition System, see the PARTITION-SPECIFIC section for programming these fields. Standard default (*97) values are shown in brackets [ ], otherwise default = 0. | | | INSTALLER CODE BURG.TRIGGER FOR RESPONSE TYPE 8...
  • Page 6 PAGER ID # FOR ALARMS 0=Ademco Low Speed; 1=Sescoa/Radionics SECONDARY FORMAT Enter up to 10 digits for the pager id # 0=Low Speed; 1=Contact ID; 2=Ademco High Speed; PAGER PHONE # FOR SUPERVISION 3=Ademco Express LOW SPEED FORMAT (Sec.) 0=Ademco Low Speed; 1=Sescoa/Radionics Enter 0-9 for each digit.
  • Page 7 PAGER PHONE # FOR OPENS/CLOSES SEC. SUBS. ACCT # Enter 00-09; B-F (11-15) [15 15 15 15] 1*17 LOBBY PARTITION Enter the "common lobby" partition (1-2) Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause 1*18 AFFECTS LOBBY PAGER ID # FOR OPENS/CLOSES...
  • Page 8 1*35 ACCESS CONTROL DIALER ENABLES 1*73 PRINTER BAUD RATE 1=300; 0=1200 [0 0 0 0 0 0] Must be 1200 if using pager interface Trace Trbl Byps Not used Syst 1*74 RELAY TIMEOUT XX MINUTES [000] 1=enable; 0=disable Enter the relay timeout, 0-127 in multiples of 2 minutes, 1*42 CALL WAITING DEFEAT desired for #80 Menu Mode time driven event relay...
  • Page 9: Partition-Specific

    2*10 3*17 ALLOW DISARMING ONLY DURING ALTERNATE FUNCTION (TAMPER) ARMING/DISARMING WINDOWS FOR ZONE 6 0=disabled; 1=enabled 0=disable; 1=enable 3*18 EXTENDED DELAY FOR TYPES 17&18 See system-wide field 2*11 if enabling field 2*10. This feature adds high security to the installation. 0=No;...
  • Page 10: Partition-Specific Fields

    SUMMARY OF PROGRAMMING COMMANDS • To enter program mode, enter installer code + [8] + [0] + [0] • To set standard defaults, press *97 • To change to next page of program fields, press *94 • To return to previous set of fields, press *99 •...
  • Page 11 2nd Page Fields 2*10 ALLOW DISARMING ONLY DURING 1*26 PANIC BUTTON OR SPEEDKEY ARMING/DISARMING WINDOWS See system-wide field 2*11 if enabling field 2*10. This [00, 00, 00, 00] feature adds high security to the installetion. 0=disable; 1=enable Enter speedkey macro # (01-35) to use keys A-C for macro. 2*18 ENABLE GOTO FOR THIS PARTITION Otherwise enter 00 to use as panic.
  • Page 12: Programming With #93 Menu Mode

    Programming With #93 Menu Mode NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should be programmed via Device programming. After programming all system related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu driven programming functions.
  • Page 13: Zone Programming

    For entering voice descriptors for relays to be used with the 4285/4286 VIP Module. RLY VOICE DESCR? 1 = YES 0 = NO For creating custom word substitutes for VIP Module annunciation. CUSTOM INDEX ? 1 = YES 0 = NO For defining the parameters for each of the VistaKey access point including which group(s) ACCESS POINT PGM have access through an access point (door).
  • Page 14: Communications

    Each zone must be assigned a zone type, which defines the way in which the system responds 010 ZONE TYPE to faults in that zone. Refer to the Zone Type Definitions section in the VISTA-32FB PERIMETER Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary).
  • Page 15 If response type 27 selected, this prompt will be displayed. Enter whether the access point is 010 ENTRY OR EXIT an entry or exit point. 0 = entry; 1 = exit Each zone can be assigned to activate either one or both bell outputs and/or the system's 010 BELL/RLY SEL auxiliary relay.
  • Page 16: 5800 Series Transmitters Loop Designations

    5800 Series Transmitters Loop Designations LOOP 3 LOOP LOOP (REED) (PRIMARY) LOOP 2 LOOP 1 (TERMINALS) (AUX. CENTER) LOOP 1 LOOP (AUX. RIGHT) LOOP 4 ALTERNATE YOU MUST 5 8 1 6 M N POSITION 5 8 1 7 ENROLL THIS ENROLL AS "RF"...
  • Page 17: Menu Mode

    If the serial number transmitted does not match the serial number entered, a display Entd A022-4063 similar to the one at the left will appear. If the loop number does not match, it will also be Rcvd A022-4064 displayed. If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary display does not appear), press the [#] key twice and then enter or transmit the correct serial number.
  • Page 18 Enter all zone information except for Loop number, or press “C” to copy the zone information ZT P RC on this screen from last saved zone (including Loop). 010 03 ZT = Zone Type = Partition RC = Report Code In = Input Device Type = Loop number to which the sensor is connected.
  • Page 19 To Delete a Serial Number 010 INPUT S/N: To delete an existing serial number, enter “0“ in the loop number field. The serial number will A000-0000 change to “0”s. If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display.
  • Page 20 Use the [A] key to move forward within the screen, and the [B] key to back up If YES was entered at the SET TO CONFIRM prompt previously (see first prompt following XMIT TO CONFIRM entry into the Expert Programming Mode), the display on the left will appear. PRESS TO SKIP To confirm, activate the button on the wireless key that corresponds to this zone.
  • Page 21: Menu Mode

    All report codes are entered using # 93 Menu Mode Programming , either through Report Code Programming or through the Zone Programming while entering other zone information. In the VISTA-32FB, reports are divided into six categories. These categories represent the main menu options found in Report Code Programming . Reports and the categories in which they...
  • Page 22 Restore/Supervisory Codes Press 1 (YES) to enter Restore and Supervisory Codes for zones. RESTR, SUPV. CODE 1 = YES 0 = NO Enter one zone for each group of 16 zones (001-016, 017-032). ENTER ZN FOR GRP 000 = QUIT Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry).
  • Page 23: Menu Mode

    System Group #2 Codes To enter System Group #2 codes, press 1 (YES). SYSTEM GROUP #2 ? 1 = YES 0 = NO Enter the first digit of the Arm-STAY report. Press [ ]. Enter the second digit of the report. If STAY the user number is desired as the second digit, enter 01 (not necessary for Contact ID or High- 1st 00...
  • Page 24: Menu Mode

    Alpha Descriptors Programming General Information • A user-friendly English language description/location for all protection zones, Outputs, keypad panics, polling loop short, and RF receiver supervision troubles can be programmed. • Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an s or 's added to it.
  • Page 25 To add an s or 's , if needed, press 2 . The first depression adds an s , the second depression adds an ' s , the third depression displays no character (to erase the character), the fourth depression adds an s , etc. Accept the word.
  • Page 26 Custom Words Up to 60 installer-defined words can be added to the built-in vocabulary. Each of the 60 words can actually consist of several words, but bear in mind that a maximum of 10 characters can be used for each word string. Select CUSTOM WORD Mode.
  • Page 27: Alpha Descriptor Vocabulary

    Alpha Descriptor Vocabulary (For Entering Alpha Descriptors. To select a word, press [#] followed by the word's 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the RELAY VOICE DESCRIPTORS section when programming relay voice descriptors. 000 (Word Space) 107 HOUSE 158 PHOTO...
  • Page 28: Device Programming

    Device Programming This menu is used to program keypads, receivers and relay modules. From Data Field Programming Mode, press #93 to display "ZONE PROG?". Press 0 repeatedly to display "DEVICE PROG?". Press 1 to enter Device Programming . DEVICE PROG? 1=YES 0=NO The device address identifies the device to the control.
  • Page 29 Output Relay Module If device type 4 (relay module) is selected, this prompt will appear. Enter 1 if the unit is a SUPERVISED CF? 4204CF. If not, enter 0. If 1 is entered, only Relay 1 (Output A) and relay 3 (Output B) on each module are able to be programmed for functions.
  • Page 30: Menu Mode

    The 6139 Keypad will display the following prompts, which are sent by the Long Range Radio transmitter to the control. Note: These prompts are for the 7820 Radio only. If you are using a different radio, refer to the radio’s instructions for the correct prompts.
  • Page 31: Output Programming

    Output Programming The system supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each output must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a designated STOP event.
  • Page 32: Communications

    Output Devices Programming From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press 0 (NO) to each menu option until the "OUTPUT PGM?" prompt appears. Press 1 (YES). While in this mode, press [ ] to advance to next screen. Press [#] to backup to the previous screen. Enter the Output identification number 01-96.
  • Page 33 If using options 56 or 57 (usually as the STOP Zone Type), data fields 1 74 and 1 75 for the respective relay timeouts for minutes and seconds must be programmed. If the start zone type selected was 27 (access point), this prompt will be displayed. Enter the 02 START: ACS PT access point (00-31) which will start the Output action.
  • Page 34: Menu Mode

    Enter the LED number on the FSA module (01-08 for FSA-8; 01-24 for FSA-24). 01 LED # Press [ ] to continue. The keypad will display the Start and Stop summary screens again. Press [ ] to continue. When all output devices have been programmed, enter 00 at the "ENTER OUTPUT #." prompt. If defining a zone list, continue to the next section.
  • Page 35: Relay Voice Descriptors And Custom Word Substitutes Vocabulary

    Press 1 to program voice descriptors for relays. RLY VOICE DESCR? 1=YES 0=NO Enter the 2-digit relay number (01-16) for the Output desired, or enter 00 to quit Relay Voice ENTER RELAY NO. Descriptor Programming Mode. 00=QUIT Press [ ] From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3- 01 ENTER DESC d1 digit index number for the first word of the relay descriptor phrase.
  • Page 36: System Layout Worksheets

    Custom Word Substitutes for VIP Module Annunciation A substitute word can be programmed for each of the 60 custom words used in your alpha zone descriptions. The VIP Module will announce this substitute word in place of the custom word that is displayed on the alpha keypad. For example, an alarm display of "John's Bedroom"...
  • Page 37 SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no) Option Part. 1 Part. 2 Entry Delay #1 (15-225 seconds): Exit Delay #1 (15-225 seconds): Entry Delay #2 (15-225 seconds): Exit Delay #2 (15-225 seconds): Quick Arming Multiple Alarms per Arming Console Panic for zone 995 ( + 1) Console Panic for zone 996 (# + 3) Console Panic for zone 999 ( + #) Allow Sign-on (GOTO function)
  • Page 38 DEVICES (keypads, 4204, rf receivers, vip module, lrr, vgm) Device Home Sound Supv Keypad Device Home Sound Supv Keypad Address Type Part Global Address Type Part Global Type: Console Sounder Options: 0 = Device Not Used 00 = No Suppression 1 = Alpha Console 01 = Suppress Arm/Disarm and Entry/Exit Beeps 3 = RF Receiver...
  • Page 39 ZONE DEFINITIONS FOR ZONES 001-027 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-2) (1-13) Loop Activation Code Alpha Descriptor (3 words max.) — 39 — www.PDF-Zoo.com...
  • Page 40 ZONE DEFINTIONS FOR ZONES 028-032 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) & Type (1-2) (1-13) Loop Activation Code Alpha Descriptor (3 words max.) ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, & 999 Enter yes/no for each partition-field 22 Zone...
  • Page 41 ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-616 Zone Information (part numbers) Zone Information (part numbers) Zone Zone Report & Zone Zone Report & Type Code Alpha Descriptor (3 words max.) Type Code Alpha Descriptor (3 words max.) ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-831 Zone Information (part numbers) Zone Information (part numbers) Zone...
  • Page 42 Zone Types: 00=zone not used 06=24 hour silent 16=fire w/verification 21=arm away 01=entry/exit 1 07=24 hour audible 17=fire waterflow 22=disarm 02=entry/exit 2 08=24 hour auxiliary 18=fire supervisory 23=no alarm response 03=perimeter 09=supervised fire 19=24 hour trouble 27=access control 04=interior (follower) 10=interior (delay) 20=arm stay 28=MLB supervision...
  • Page 43: Output Devices Programming

    Output Devices Programming Applicable only if Relays (4204/4204CF), FSA Modules, or V-Plex Relays (4101SN) are used. Output Devices – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 44 OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for 1=4204 4204 or Output Restrict 3=FSA Dev Add 4204 LED # for OUTPUT EV/ZL Zone ZT / P ZT / P Group or FSA DEV #...
  • Page 45 OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for 1=4204 4204 or Output Restrict 3=FSA Dev Add 4204 LED # for OUTPUT EV/ZL Zone ZT / P ZT / P Group or FSA DEV #...
  • Page 46 OUTPUT DEVICES WORKSHEET (cont’d) S T A R T S T O P 0=V-Plex V-Plex Zone # Relay # for 1=4204 4204 or Output Restrict 3=FSA Dev Add 4204 LED # for OUTPUT EV/ZL Zone ZT / P ZT / P Group or FSA DEV #...
  • Page 47: Communications

    0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 = DEVICE ACTION Toggle alternately between START and STOP events. EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore 1-15, 0 = Not Used.
  • Page 48: Menu Mode

    ZONE LISTS FOR OUTPUT DEVICES – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence. Up to 15 zone lists may be created.
  • Page 49 Zone List 10: Started or stopped by zone numbers (enter 000 to end entries). Zone List 11: Started or stopped by zone numbers (enter 000 to end entries). Zone List 12: Started or stopped by zone numbers (enter 000 to end entries). Zone List 13: Started or stopped by zone numbers (enter 000 to end entries).
  • Page 50: Scheduling Menu Prompts

    Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the menu driven programming functions. Only users with an Installer or Master level user code may enter the #80 mode. Press 0 (NO) or 1 (YES) in response to the displayed menu selection.
  • Page 51: Scheduling Worksheets

    Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 52 Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 53 Below is a list of the "Action" codes (desired actions) used when programming time driven events. Note that these codes are independent of the "Output codes" programmed during the #93 Menu Mode–Output Programming mode. If using Time Driven Events to control Outputs, the following menu items must first be programmed using #93 Menu Mode - Output Programming: Enter Output No.
  • Page 54 Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
  • Page 55 NOTE 2: TO OTHER DEVICES Ratings: 10 - 14VDC, 1.7A max. 2k EOLR is Ademco model 610-7 - Zones 1, 2, 8: 100 ohms max - 2mA max for smoke det. (up to 16 detectors See note 1, see instructions...
  • Page 56 165 Eileen Way, Syosset, NY, 11791 Copyright © 2000 PITTWAY Corporation ¬.9'l K3840V1 9/00 www.PDF-Zoo.com...

Table of Contents