ADEMCO VISTA-32FB Quick Start Manual
ADEMCO VISTA-32FB Quick Start Manual

ADEMCO VISTA-32FB Quick Start Manual

Commercial fire and burglary partitioned security system with scheduling

Advertisement

9
,
6
7
$



)
%
9
,
6
7
$



)
%
&RPPHUFLDO)LUHDQG%XUJODU\
3DUWLWLRQHG6HFXULW\6\VWHP
ZLWK6FKHGXOLQJ
4XLFN6WDUW*XLGH
FIRE
FIRE
PULL
K3840 3/99

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VISTA-32FB and is the answer not in the manual?

Questions and answers

Summary of Contents for ADEMCO VISTA-32FB

  • Page 1 &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 4XLFN6WDUW*XLGH FIRE FIRE PULL K3840 3/99...
  • Page 2 – 2 –...
  • Page 3: Table Of Contents

    • To enter Program mode, enter [Installer Code] + [8] + [0] + [0] • To set standard defaults, press 97 • To set communication defaults, press 94 + one of the following: 80=low speed; 81=ADEMCO Express; 82=ADEMCO High Speed; 83=ADEMCO's Contact ID •...
  • Page 4: Recommended Programming Procedure

    Recommended Programming Procedure The following is a step-by-step procedure recommended for programming your VISTA-32FB system. 1. Set the keypads (and other peripheral devices) to the appropriate addresses. 2. Set factory defaults by pressing 97. This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these addresses.
  • Page 5 12. Define user access codes. Refer to SECTION 28: USER ACCESS CODES to program authority level, O/C reporting option, partition assignments, and wireless key assignments for each user. 12. Exit Programming mode. Exit Programming mode by pressing either 98 or 99. An additional entry of 99 is required if the exit is being done from fields 1 00 and above.
  • Page 6: Program Field Categories

    Program Field Categories In the following pages, the programming fields have been arranged by category. Use this index to cross reference the numerically ordered fields on the Programming Form. Field Group Field Group Field Group System-Wide Communications 1 57 System-Wide System-Wide Communications 1 58...
  • Page 7: Vista-32Fb Programming Form

    VISTA-32FB Programming Form Some fields are programmed for each partition (shown as shaded fields). If programming a multiple-partition system, see the PARTITION-SPECIFIC section for programming these fields. Standard default ( 97) values are shown in brackets [ ], otherwise, default = 0.
  • Page 8 PRIMARY FORMAT Enter 0-9 for each digit. Enter #11 for , #12 for #, #13 for 2-second pause. 0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed; 3=ADEMCO Express. PAGER ID # FOR ALARMS LOW SPEED FORMAT (Primary) 0=ADEMCO Low Speed; 1=Sescoa/Radionics.
  • Page 9 Enter 1 if arming this partition attempts to arm lobby; enter 0 PAGER PHONE # FOR SYSTEM if it does not. Must be 0 for Commercial Fire and UL installations. 1 20 EXIT ERROR LOGIC 0=no; 1=bypass E/E and Interior zones faulted after exit delay.
  • Page 10 1 45 1 77 EXIT DELAY SOUNDING LOG FIRST MAINTENANCE SIGNAL 1=enable; 0=disable. Produces quick beeping during exit 0=no log; 1=log first maintenance signal from each smoke delay if enabled. detector 1 47 CHIME ON BELL 1 3rd Page Programming Fields (press 1=enable;...
  • Page 11 (Waterflow and FIre Supv) Enter 00-15 times 2 seconds. following: 80=low speed; 81=ADEMCO Express; 3 17 ALTERNATE FUNCTION (TAMPER) 82=ADEMCO High Speed; 83=ADEMCO's Contact ID • To change to next page of program fields, press FOR ZONE 6 0=disabled; 1=enabled.
  • Page 12: Partition-Specific Fields

    Partition-Specific Fields (Duplicate this page for each partition in the installation.) To program these fields: 1. Press 91 to select a partition. 2. Enter a partition-specific field number (e.g., 09). 3. Make the required entry. 4. Repeat steps 1-3 for each partition in the system. PARTITION #____ PROGRAM FIELDS 1st Page Fields ENABLE DIALER REPORTS[0]...
  • Page 13 ARMING/DISARMING WINDOWS following: 80=low speed; 81=ADEMCO Express; See system-wide field 2 11 if enabling field 2 10. This 82=ADEMCO High Speed; 83=ADEMCO's Contact ID feature adds high security to the installation. • To change to next page of program fields, press 0=disable;...
  • Page 14: Programming With #93 Menu Mode

    Programming With #93 Menu Mode #93 Main Menu Options The following fields should be programmed before beginning: 2 00: Number of Partitions. For Commercial Fire and UL installations, verify that wireless and audio alarm verification features are disabled. After programming all system-related programming fields in the usual way, press # 93 while still in Programming Mode to display the first choice of the menu-driven programming options, which are as follows: For programming the following:...
  • Page 15 For defining the following device characteristics for addressable DEVICE PROG? devices, including keypads, RF receivers (5881), and 4204 0=No 1=Yes Output Relay Modules: • Device address. • Device type. • Keypad options (includes partition assignment). • RF House ID. For defining output relay functions. RELAY PROG? 0=No 1=Yes...
  • Page 16 Enter 1, if a program tool is being used. If not, enter 0. When PROGRAM TOOL? a 0 is entered, the system will advance to the ENTER ZN NO. 0 = NO, 1 = YES prompt. The system will prompt for the unit’s serial number, if a 1 is 000 INPUT S/N: L entered.
  • Page 17 ↓ Zone Number Each zone must be assigned a zone type, which defines the way 010 ZONE RESPONSE in which the system responds to faults in that zone. Refer to Perimeter the Zone Type Definitions section for detailed definitions of Zone Type 03 entry shown each zone type.
  • Page 18 Enter the input device type as follows: 010 INPUT TYPE 00 = not used RF Xmitter 01 = hardwired Note that input types 4 03 = supervised RF transmitter (RF type) and 5 are valid for 04 = unsupervised RF transmitter (UR type) certain 5800 Series 05 = RF button-type transmitter (BR type) transmitters only (e.g.,...
  • Page 19: 5800 Series Rf Transmitter Loop Designations

    5800 Series RF Transmitter Loop Designations LOOP LOOP LOOP (REED) (REED) LOOP 1 LOOP 1 (TERMINALS) (TERMINALS) LOOP ALTERNATE 5 8 1 6 5 8 1 6 M N (ALWAYS USE) POSITION ENROLL AS "RF" ENROLL AS "RF" FOR LOOP 2 5 8 0 2 / 5 8 0 2 C P ENROLL AS "BR"...
  • Page 20 This prompt is displayed if 1 (Yes) is entered in response to the 010 INPUT S/N LEARN S/N? prompt. The serial number may be enrolled by Axxx-xxxx one of two methods: a) Enter the 7-digit serial number printed on the device using an alpha keypad.
  • Page 21 1. Enter Data Field Programming Mode: [Installer Code] + [8 0 0]. 2. From Data Field Programming Mode, press #93 to display the ZONE PROG? prompt. 3. Press 0 (NO) repeatedly until the SEQUENTIAL LEARN? prompt appears. To enroll or delete a device's serial number, enter 1 (YES). SEQUENTIAL LEARN? Enter 0 to skip to the next main menu option.
  • Page 22 If the first zone number entered does not have all of the above attributes, the system will search its database for the first zone that does and will display it on the next screen. This prompt is displayed when the system has found the next 010 INPUT S/N zone that needs to be enrolled.
  • Page 23 All report codes are entered using # 93 Menu Mode Programming, either through Report Code Programming or through the Zone Programming while entering other zone information. In the VISTA-32FB, reports are divided into six categories. These categories represent the main menu options found in Report Code Programming.
  • Page 24 The programming sequence that follows assumes that all reports for the system will be entered at one time. In actuality, it is possible to skip from one main menu option to another by pressing 0 (NO) at each main menu option. Main menu options are highlighted in bold text. To enter report codes, do the following: Enter Program Mode [Installer Code] + [8 0 0].
  • Page 25 Enter the first digit of the Trouble Restore Code (single-digit TROUBLE RESTORE GRP 001-016 entry) and press [ ]. The second digit will be the ID (second) digit of the Alarm Report Code for each zone (if programmed). Press [ ] to continue. Enter the first digit of the Bypass Report Code (double-digit BYPASS GRP 001-016...
  • Page 26 System Group 2 Codes To enter System Group #2 codes, press 1 (YES). SYSTEM GROUP #2 ? 1 = YES 0 = NO Enter the first digit of the Arm-STAY report. Press [ ]. Enter STAY 1st 00 2nd 00 the second digit of the report.
  • Page 27 System Group 4 Codes To enter System Group #4 codes, press 1 (YES). SYSTEM GROUP #4 ? 1 = YES 0 = NO Enter the first digit of the Fire Test Start Report Code. Press WALK TEST START 1st 00 2nd 00 [ ].
  • Page 28 CUSTOM WORD? for creating custom words for use in descriptors. PART DESCRIP? for creating 4-character partition names. EXIT EDIT MODE? Press 1 to exit back to # 93 Menu Mode. 4. Refer to the sections that follow for procedures for adding alpha descriptors. Zone Descriptors 1.
  • Page 29 6. Store the descriptor. When all desired words have been entered, press 8 to store the description in memory. To review the zone descriptors, press [#] + [zone number] (e.g., #001). To edit zone descriptors, press [ ] + [zone number] (e.g., 001). 7.
  • Page 30 When using method 3b to enter alpha descriptors, each word will be found at the end of the group of words that begin with the same letter as it does. 6. Repeat steps 2 through 6 to create up to 20 custom words (or word strings). 7.
  • Page 31: Alpha Descriptor Vocabulary

    ALPHA DESCRIPTOR VOCABULARY For entering alpha descriptors. To select a word, press [#] followed by the word's 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when programming relay voice descriptors. 000 (Word Space) 107 HOUSE 210 THERMOSTAT...
  • Page 32: Device Programming

    Device Programming This menu is used to program keypads, receivers, and relay modules. From Data Field Programming Mode, press #93 to display ZONE PROG?. Press 0 repeatedly to display DEVICE PROG?. It is very important that devices programmed into the panel in device programming MATCH what is wired to the keypad connections.
  • Page 33 If device type 1 (alpha keypad) is entered, this prompt will SOUND OPTION appear. Keypads can be individually programmed to suppress arm/disarm beeps, entry/exit beeps and Chime mode beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises. Enter a number 00-03 for the keypad sounding suppression options desired for the keypad as follows: 00 = no suppression.
  • Page 34 Long Range Radio If device type 6 is chosen, the 6139 Keypad will function similar to the 7720PLRR Programming Tool. See the figure below for the functions of the keys on the 6139. ARMED READY BS/ESC SPACE ENTER SHIFT SHIFT function indicated by turning on READY LED. Each key has two possible functions: a normal function and a SHIFT function.
  • Page 35 The 6139 Keypad will display the following prompts, which are sent by the Long Range Radio transmitter to the control. Enter the device address of the radio. The default address is 3. DEVICE ADDRESS Enter the 4-digit customer account number, 0001-9999. If the ID # answer to the USE RADIO prompt is N, this ID number will (1234)
  • Page 36 VIP Module If device type 5 (VIP Module) is selected, this prompt will MODULE PART. appear. Enter the partition number 1-2 in which the module is located. Press [ ] to accept entry. Press 00 + [ ] to exit Menu Mode. Press 99 to exit Program Mode.
  • Page 37 2) ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device have the same response type, and there are no other zones of this type that are not to activate this device, then ZONE TYPE may be used instead of using a ZONE LIST and EVENT to activate the device.
  • Page 38 Relay Output Devices Programming From Data Field Programming Mode, press #93 to display the ZONE PROG? prompt. Press 0 (No) in response to each menu option until the RELAY PROG? prompt appears. Press 1 (Yes). While in this mode, press [ ] to advance to next screen. Press [#] to back up to the previous screen. Enter the relay (output device) identification number 01-16.
  • Page 39 Choices for Start/Stop Zone Types: Choices for Start/Stop System Operation: 00 = No Response (Not Used) 18 = Fire Supervisory 45 = Polling Loop Failure 01 = Entry/Exit #1 19 = 24-Hr. Trouble 51 = RF Receiver Failure 02 = Entry/Exit #2 20 = Arming-STAY 52 = Kissoff 03 = Perimeter...
  • Page 40 Relays may be grouped for common activation by time-driven RELAY GROUP events (commands 06-10). Enter 0 (no group) or 1-8 for a specific group number. Press [ ] to continue. If this relay is on a supervised 4204CF Module, it may be used 01 FIRE BELL? as an additional fire bell.
  • Page 41 Zone List Programming After all relays have been programmed, upon entering 00 at the ENTER RELAY NO. prompt, a zone list must be entered. If a zone list number was used to start or stop a relay, the zones belonging to that list must be defined as follows: Enter the zone list number 01-08.
  • Page 42 Press 1 to program voice descriptors for relays. RLY VOICE DESCR? 0=no 1=yes Enter the 2-digit relay number (01-16) for the relay desired, or ENTER RELAY NO. enter 00 to quit Relay Voice Descriptor Programming Mode. 00=QUIT Press [ ]. From the Relay Voice Descriptor and Custom Word Substitutes 01 ENTER DESC d1 Vocabulary List, enter the 3-digit index number for the first...
  • Page 43: Relay Voice Descriptors And Custom Word Substitutes Vocabulary

    Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word Index Word Index Word Index Word Index Word Index Air ....116 Daughter's ..208 Front ....087 No..... 165 Side ....153 Alarm ....255 Den....052 North....146 Six ..... 075 And....
  • Page 44 Custom Word Substitutes for VIP Module Annunciation A substitute word can be programmed for each of the 20 custom words used in your alpha zone descriptions. The VIP Module will announce this substitute word in place of the custom word that is displayed on the alpha keypad.
  • Page 45: System Layout Worksheets

    System Layout Worksheets As with any security system, you should first define the installation. This includes determining how many partitions will be used, how many zones per partition, and how many users per partition. You will also need to determine what peripheral devices will be needed, and basic system options such as exit/entry delays, etc. The control panel itself should be located in an area that will facilitate wire runs to all partitions, and will allow access to power and telephone circuits.
  • Page 46 SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no) Option Part. 1 Part. 2 Entry Delay #1 (15-225 seconds): Exit Delay #1 (15-225 seconds): Entry Delay #2 (15-225 seconds): Exit Delay #2 (15-225 seconds): Quick Arming Multiple Alarms per Arming Keypad Panic for Zone 995 ( + 1) Keypad Panic for Zone 996 (# + 3) Keypad Panic for Zone 999 ( + #) Allow Sign-on (GOTO function)
  • Page 47 DEVICES (keypads, 4204, RF receivers, VIP module, LRR) Device Home Sound Supv Keypad Device Home Sound Supv Keypad Address Type Part Global Address Type Part Global Type: Keypad Sounder Options: 0 = Device Not Used 00 = No Suppression 1 = Alpha Keypad 01 = Suppress Arm/Disarm and Entry/Exit Beeps 3 = RF Receiver 02 = Suppress Chime Mode Beeps Only...
  • Page 48 ZONE DEFINITIONS FOR ZONES 001-024 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) and Type (1-2) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) – 48 –...
  • Page 49 ZONE DEFINITIONS FOR ZONES 025-032 Parti- Input Serial # Zone Zone tion Type Device Bell/Relay Report Zone Information (part numbers) and Type (1-2) (1-8) Loop Activation Code Alpha Descriptor (3 words max.) Bell/Rel Zone Zone Report Zone Information (part numbers) Type Code Act.
  • Page 50 ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-616 Zone Information (part numbers) Zone Information (part numbers) Zone Zone Report Zone Zone Report Type Code Alpha Descriptor (3 words max.) Type Code Alpha Descriptor (3 words max.) – 50 –...
  • Page 51 ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-830 Zone Information (part numbers) Zone Information (part numbers) Zone Zone Report Zone Zone Report Type Code Alpha Descriptor (3 words max.) Type Code Alpha Descriptor (3 words max.) Zone Types: 00=Zone Not Used 06=24-Hour Silent 16=Fire W/Verification 21=Arm Away 01=Entry/Exit 1...
  • Page 52: Output Relays Worksheets

    Output Relays Worksheets Applicable only if relays (4204/4204CF) are to be used. Output Devices – Programmed in #93 Menu Mode Programming in Relay Programming. Fill in the required data on the worksheet below and follow the procedure in the Installation Instructions as you enter the data in response to the displays and prompts that appear in sequence.
  • Page 53 ZT = ZONE TYPE/SYSTEM OPERATION Choices for Zone Types are: 00=Zone Not Used 06=24-Hour Silent 17=Fire Waterflow 01=Entry/Exit 1 07=24-Hour Audible 18=Fire Supervisory 02=Entry/Exit 2 08=24-Hour Auxiliary 19=24-Hour Trouble 03=Perimeter 09=Supervised Fire 23=No Alarm Response 04=Interior (Follower) 10=Interior (Delay) 05=Day/Night Burglary 16=Fire w/Verification Any zone in "ZT"...
  • Page 54: Scheduling Menu Prompts

    Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [Installer Code] + # + 80 to display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection.
  • Page 55: Scheduling Worksheets

    Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the Installation Instructions as you enter the data in response to the displays and prompts that appear in sequence.
  • Page 56 Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the Installation Instructions as you enter the data in response to the displays and prompts that appear in sequence.
  • Page 57 Below is a list of the "Action" codes (desired actions) used when programming time-driven events. Note that these codes are independent of the "relay codes" programmed during the #93 Menu Mode–Relay Programming mode. If time-driven events are being used to control relays, the following menu items must first be programmed using #93 Menu Mode - Relay Programming: Enter Relay No.
  • Page 58 Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system. Fill in the required data on the worksheet below and follow the procedure in the Installation Instructions as you enter the data in response to the displays and prompts that appear in sequence. Tues Thurs Temporary Schedule #81 Menu Mode The system provides a Temporary Schedule for each partition.
  • Page 59: Vista-32Fb Summary Of Connections

    VISTA-32FB SUMMARY OF CONNECTIONS – 59 –...
  • Page 60 165 Eileen Way, Syosset, NY 11791 Copyright © 1999 PITTWAY CORPORATION ¬.l K3840 03/99...

Table of Contents