INSTALLATION

Mounting of indoor unit

z
Please refer to the installation manual provided with the indoor unit for mounting.
Please refer to the diagram below for installation height.
When installing this product to existing indoor units, please adjust the installation height of the
indoor units to height 230-235mm.
Indoor unit
Fresh air intake kit
Pre-installation preparations
z
Please attach the duct flange provided with screws.
The Fresh Air Intake Kit can be used with an external air intake on just one side. Use included
sealed plate to apply for different eye holes.
Please apply Insulation
[When taking in the air in two sides]
Please paste the insulation in the order shown in the figure below.
2
1
Insulation 
 to the installed duct flange parts (Do not apply to sealed areas).
Insulation 
screw × 4 screw × 4
+
250
3
[Paste start position]
When pasting, make sure that there is no gap
between the INSULATION  (overlap is allowed)
(Unit : mm)
Metal hanging fastener
Ceiling
Overlap with each other
Insulation 
mm
20
0
Insulation 
Insulation 
Cut the insulation  to
+20
250
mm and then apply.
0
- (05-91) -
2
1