Fujitsu AU*G36LRLA Design & Technical Manual page 288

Fujitsu 3 phase type single / simultaneous multi system
Hide thumbs Also See for AU*G36LRLA:
Table of Contents

Advertisement

FUNCTION SETTING
3) Pressing the SET BACK button, select a remote controller address (select the indoor unit
you want to operate).
4) Pressing the SET TIME < button or the SET TIME > button, to select the function number.
5) Pressing the SET TEMP. V button or the SET TEMP. Λ button, to select the setting number.
The display flashes during setting number selection.
6) Pressing the TIMER SET button, confirm the setting.
(The data will be transferred to the indoor unit.)
When the data was not set up on the indoor
unit (-- is displayed.)
Set up the data again according to the
procedure in step 6), 7) above.
FUNCTION DETAILS
Refer to 6-6. FUNCTION DETAILS
Remote controller address
Ex.) When remote controller address "00" is
selected
Function number
Setting number
Ex.) Function number : 30, Setting number : 01
ERROR
When the data was normally set up on the indoor
unit
(Flashing display changes to illuminated display.)
- (05-59) -
GOOD

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents