Troubleshooting
4-4-13 Option error of the Remote Controller for an Indoor Unit
Outdoor unit display
Indoor unit display
Criteria
• Display number type of indoor unit – E163 occurs, Lamp type – all lamps flash
Cause of problem
• Missed or erroneous input of remote controller options
Check relevant remote controller options for each model then enter correct options
4-4-14 Error due to confused use of Fahrenheit and Celsius
Outdoor unit display
Indoor unit display
×(Operation)
• Display number type of indoor unit – E170 occurs, Lamp type – all lamps flash
Criteria
• Occurs in an indoor unit with Celsius setting
• Missed input of remote controller options
Cause of problem
Check relevant remote controller options for each model then enter correct options
As this happens only in a Celsius setting model, it is necessary to reenter option codes for error-free models in a region where Celsius
is used.
4-4-15 Error due to incorrect Indoor Unit Power/Communication Cable Connection
Outdoor unit display
Indoor unit display
Criteria
• Check for Power input(220V) for the Terminal block(F1/F2).
Cause of problem
• Apply power (220V) to the terminal of the indoor unit communication block (F1/F2)
Check for disconnected line after turning off the Main power.
4-109
(Operation)
(Timer)
(Fan)
(Timer)
(Fan)
(wall mount type)
(Filter)
(Defrost)
(Filter)
×(Defrost)