INSTALLATION
MANUAL
Cassette Type Series
1 way cassette : AVXC1
2 way cassette : AVXC2
4 way cassette : AVXC4
Air Conditioner



AVXCM
 (mini)

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AVXC1 Series

  • Page 1 INSTALLATION MANUAL Cassette Type Series 1 way cassette : AVXC1  2 way cassette : AVXC2  4 way cassette : AVXC4  AVXCM  (mini) Air Conditioner DB98-27703A(1)
  • Page 2: Table Of Contents

    Contents Safety Precautions .................. Accessories ...................... Selecting the Installation Location ............ Indoor Unit Installation ................12  Purging the Unit ..................... 14  Connecting the Refrigerant Pipe ............15  Cutting/Flaring the Pipes ................16  Performing Leak Test & Insulation ............17 ...
  • Page 3: Safety Precautions

    Safety Precautions The following safety precautions must be taken when using your air conditioner. • Risk of electric shock can cause injury or death. • Disconnect all remote electric power supplies before servicing, WARNING installing or cleaning. • Installation must be done by the manufacturer or service agent or a similar qualified person in order to avoid a hazard.
  • Page 4 Safety Precautions (Continued) CAUTION Make sure that you earth the cables.  - Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, electric shock or fire may occur. Install the circuit breaker.
  • Page 5: Accessories

    Accessories The following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications. AVXC1/AVXC2 Pattern sheet Insulation refrigerant Insulation cover drain Flexible hose Insulation drain pipe Rubber Insulation cover band Installation manual AVXC4 Pattern sheet Insulation cover drain Insulation...
  • Page 6: Selecting The Installation Location

    Selecting the Installation Location Indoor Unit  There must be no obstacles near the air inlet and outlet.  Install the indoor unit on a ceiling that can support its weight.  Maintain sufficient clearance around the indoor unit.  Make sure that the water dripping from the drain hose runs away correctly and safely.
  • Page 7 Dimension of the indoor unit AVXC1 Unit : mm Name Description  Liquid pipe connection ø6.35 (1/4”)  Gas pipe connection ø12.70 (1/2”)  Drain pipe connection VP20 (OD ø26, ID ø20)  Power supply connection  Air discharge grille ...
  • Page 8 Selecting the Installation Location (Continued) Dimension of the indoor unit AVXC2 Unit : mm 136.5 1030 Name Description 056: ø6.35 (1/4”)  Liquid pipe connection 071: ø9.52 (3/8”) 056: ø12.70 (1/2”)  Gas pipe connection 071: ø15.88 (5/8”)  Drain pipe connection VP25 (OD ø32, ID ø25) ...
  • Page 9 AVXC4 (Type A) Unit : mm 056/071 112/128/140 Name Description 056: ø6.35 (1/4”)  Liquid pipe connection 071/112/128/140: ø9.52 (3/8”) 056: ø12.70 (1/2”)  Gas pipe connection 071/112/128/140: ø15.88 (5/8”)  Drain pipe connection VP25 (OD ø32, ID ø25)  Power supply connection ...
  • Page 10 Selecting the Installation Location (Continued) AVXC4 (Type B) Unit : mm Name Description  Liquid pipe connection ø9.52 (3/8”)  Gas pipe connection ø15.88 (5/8”)  Drain pipe connection VP25 (OD ø32, ID ø25)  Power supply connection  Air discharge grille ...
  • Page 11 AVXCM Unit : mm Name Description  Liquid pipe connection ø6.35 (1/4")  Gas pipe connection ø12.70 (1/2”)  Drain pipe connection VP25 (OD ø32, ID ø25)  Power supply connection  Air discharge grille  Air suction grille...
  • Page 12: Indoor Unit Installation

    Indoor Unit Installation It is recommended to install the Y-joint before installing the indoor unit. Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. Note Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity.
  • Page 13 Screw eight nuts to the suspension bolts making space for hanging the Washer indoor unit. CAUTION You must install the suspension bolts more than four when installing the indoor unit. Rubber Fasten the nut Check the level of the indoor unit by using a leveler. A tilt of the indoor unit may cause malfunction of a built-in float switch ...
  • Page 14: Purging The Unit

    Purging the Unit Gas refrigerant port Liquid refrigerant port...
  • Page 15: Connecting The Refrigerant Pipe

    Connecting the Refrigerant Pipe There are two refrigerant pipes of differing diameters: A smaller one for the liquid refrigerant   A larger one for the gas refrigerant  The inside of copper pipe must be clean & has no dust. Before connecting the reprigerant pipe, open the cover side.
  • Page 16: Cutting/Flaring The Pipes

    Cutting/Flaring the Pipes Make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder) If you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe. There are some examples of correctly and incorrectly cut edges below.
  • Page 17: Performing Leak Test & Insulation

    Performing Leak Test & Insulation Leak Test To check for gas leaks on the indoor unit, check the connection part of each refrigerant pipe by using Nitrogen gas. Note See details on the outdoor unit installation manual for leak test. Leak check ...
  • Page 18 Performing Leak Test & Insulation (Continued) Select the insulation of the refrigerant pipe.  Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.  The thickness according to the pipe size is a standard of the indoor temperature of 27°C and humidity of 80%.
  • Page 19: Drainpipe And Drain Hose Installation

    Drain pipe and Drain Hose Installation Insulation drainpipe Drain hose port Adhesives Band Flexible Band Drainpipe hose...
  • Page 20 Drain pipe and Drain Hose Installation (Continued) Drainpipe Connection Flexible hose Installation The drain pipe should be installed within 100mm from the flexible hose, lift up from 100mm to 550mm and lift down 20mm or more. Be horizontal Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1~1.5m.
  • Page 21 Testing the Drainage You should test drainage after completing the installation. Prepare a little water about 1.0 liter. AVXC1 Air outlet Open the cover water supply intake. Pour water into the water supply intake. Operate the unit in the Cool mode and check a drain pump pumping. Leveler Check drain water drops at the end of the drainpipe.
  • Page 22: Wiring Work

    Wiring Work Power and communication cable connection Before wiring work, you must turn off all power source. Indoor unit power should be supplied through the breaker(MCCB, ELB) separated by the outdoor power. The power cable should be used only copper wires. Connect the power cable{1(L), 2(N)} among the units within maximum length and communication cable(F1, F2) each.
  • Page 23 Specification of electronic wire Rating current Communication Power supply MCCB Power cable Earth cable cable Unit Model Rating current X A, 30mmA Max : 242V 2.5mm 2.5mm 0.75~1.5mm AVXC1 0.18A 022 Min : 198V 0.1 sec 0.20A 028  Decide the capacity of ELB and MCCB by below formula. 0.23A 036...
  • Page 24 Wiring Work (Continued) CAUTION Select the power cable in accordance with relevant local and national  regulations. Wire size must comply with local and national code.  For the power cable, use the grade of H07RN-F or H05RN-F materials.  ...
  • Page 25: Indoor Unit Setting

    Indoor Unit Setting Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan. The address of the indoor unit is assigned by adjusting MAIN(SW01, SW02) and RMC(SW03, SW04) rotary switches. SW01 SW02 SW03 SW04...
  • Page 26: Additional Functions

    Additional Functions Function Wired remote control Centralized controller Not use 1way/2way/mini 4way SW05 RPM up K1 K2 K3 K4 4way Normal Option drain pump  N/A : Not Available Function 1way/2way/mini 4way +2°C +5°C Heating thermo-off 4way +5°C +2°C Filter signal display 1000 hours 2000 hours SW06...
  • Page 27: Final Checks And User Tips

    Final Checks and User Tips To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. Check the followings.  Strength of the installation site  Tightness of pipe connection to detect a gas leak ...
  • Page 28: Troubleshooting

    Troubleshooting Detection of errors If an error occurs during the operation, one or more LED flickers and the operation is stopped except the LED.  If you re-operate the air conditioner, it operates normally at first, then detect an error again. ...
  • Page 29 LED Display Indicators Abnormal conditions Operating Green Self-diagnostic error Displayed on appropriate indoor unit (including the indoor unit not detected) which is operating Displayed on outdoor unit 1. Error of electronic expansion valve close 2. Error of electronic expansion valve open 3.