Discharge Temperature Sensor Error For A Digital Compressor (Open/Short) - Samsung AVXCSH023/032/040CE Service Manual

System air conditioner indoor unit outdoor unit
Table of Contents

Advertisement

Troubleshooting

4-3-25 Discharge Temperature Sensor error for a digital Compressor (Open/Short)

Outdoor unit display
Indoor unit display
• Refer to how to determine below
Criteria
• Digital compressor's discharge temperature sensor OPEN/SHORT defective
Cause of problem
1. How to check
It a discharge temperature
sensor connector for a digital compressor
dislocated from the PCB.
After separating the discharge
temperature sensor connector from the PCB,
measure the resistance value between
both terminals.
Does the resistance value
greatly deviate from the
temperature table?
Restart after replacing the PCB.
4-64
(Operation)
(Timer)
(Fan)
Yes
Yes
Yes
(Filter)
(Defrost)
No
Restart after connecting the connector to
the PCB
Part to measure resistance value
No
As it is due to a problem with the
discharge temperature sensor, replace it.
Temperature
Resistance
(KΩ)
(°F)
(°C)
266
130
8.9
248
120
11.2
212
100
18.5
176
80
32
140
60
59
77
25
200
68
20
242
50
10
362
32
0
553
Samsung Electronics