Olp Sensor Error (Open/Short) - Samsung AVXCSH023/032/040CE Service Manual

System air conditioner indoor unit outdoor unit
Table of Contents

Advertisement

4-4-26 OLP sensor error (Open/Short)

Outdoor unit display
Indoor unit display
Criteria
Cause of problem
1. How to check
The sensor connection parts fell
off the PCB?
Pull out the sensor part.
Measure the inter-terminal resistance
Measured resistance out of the range?
Replace the PCB and restart.
Samsung Electronics
×(Operation)
(Timer)
(Fan)
• Refer to how to determine below
• Wire breaking or failure of the relevant sensor
No
Part to measure resistance value
Yes
Yes
(Filter) ×(Defrost)
Yes
Insert the part in the PCB and restart.
Temperature
No
Replace the damaged sensor.
Troubleshooting
Resistance
(°C)
(KΩ)
130
8.9
120
11.2
100
18.5
80
32
60
59
25
200
20
242
10
362
0
553