High Pressure Temperature Sensor Error (Open/Short); Low Ppressure Temperature Sensor Error (Open/Short) - Samsung AVXCSH023/032/040CE Service Manual

System air conditioner indoor unit outdoor unit
Table of Contents

Advertisement

Troubleshooting

4-3-31 High Pressure Temperature Sensor error (Open/Short)

Outdoor unit display
Indoor unit display
• Refer to how to determine below
Criteria
• Wire breaking or failure of the relevant sensor
Cause of problem
■ How to detect OPEN/SHORT error in Low/High pressure sensor
1. During oil retrieval, omit the error detection and start detecting 5 minutes after complete operation.
2. During safety start operation, omit the error detection and start detecting 5 minutes after complete operation.
3. During defrost operation, omit the error detection and start detecting 5 minutes after complete operation
4. SHORT error detection: carry out error detection only if it is under 0.4V.
5. During refrigerant refill/retrieval, omit low pressure sensor error detection.

4-3-32 Low Ppressure Temperature Sensor error (Open/Short)

Outdoor unit display
Indoor unit display
• Refer to how to determine below
Criteria
Cause of problem
• Wire breaking or failure of the relevant sensor
■ How to detect OPEN/SHORT error in Low/High pressure sensor
1. During oil retrieval, omit the error detection and start detecting 5 minutes after complete operation.
2. During safety start operation, omit the error detection and start detecting 5 minutes after complete operation.
3. During defrost operation, omit the error detection and start detecting 5 minutes after complete operation
4. SHORT error detection: carry out error detection only if it is under 0.4V.
5. During refrigerant refill/retrieval, omit low pressure sensor error detection.
4-70
(Operation)
(Timer)
(Fan)
(Operation)
(Timer)
(Fan)
(Filter)
(Defrost)
(Filter)
(Defrost)
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents