4-3-24 Outdoor COND OUT Sensor dislocation error

1. How to diagnose
1) During Cooling operation, there will be no detection
2) During Heating operation(Each of the below conditions have to be met for at least 20 minutes.)
Average high pressure > 2.45MPa
Average low pressure > 0.83MPa
Tcond, out - Tair, out ≥ 37°F/3°C
Tair, in - Teva, out ≥ 35.6°F/2°C
Tcond, out - Tair, out < 28.4°F/-2°C
Compressor in operation &
Indoor unit operation & Thermo On
Error details
1. How to check
Are a Cond Out sensor
and a sensor holder securely attached?
Is the resistance value for
Cond Out sensor appropriate?
Are there any changes in
sensor values during stop
heating operation?
Samsung Electronics
Outdoor Cond Out sensor dislocation error
Yes
(refer to E231)
Yes
Yes
Complete
OK
OK
OK
OK
NO
OK
No
Reinsert the sensor
Re-attach the sensor holder
No
Defective sensor: replace sensor
No
Clogged sensor path :
Replace a heat exchange ASS'Y
Troubleshooting