Table 38
UPS status messages (continued)
Event Message
BCB open
Battery Float Charging
Battery Boost Charging
Battery Discharging
Battery Period Testing
Batt. Capacity Testing
Batt. Maint. Testing
Inverter in Setting
Rectifier in Setting
Batt. Converter Fault
Operation Invalid
Byp. Abnormal Shutdown
Mains Neutral Lost
Battery Room Alarm
Rec Flash Update
Inv Flash Update
Monitor Flash Update
LBS abnormal
®
Liebert
eXM
Description / Suggested Action (if any)
BCB open from dry contact signal.
Battery is float charging.
Battery is boost charging.
Battery is discharging.
Battery is period self-testing.
Battery is capacity self-testing.
Battery is maintenance self-testing.
Inverter is in parameter setting.
Rectifier is in parameter setting.
Battery converter output voltage beyond limits or battery fuse failed. Battery converter shuts
down. Battery backup not available.
This record is registered following an incorrect operation.
Both bypass and inverter voltages unavailable. Load interruption.
AC Input mains reference neutral not detected.
Environment in battery room needs attention.
Rectifier firmware is being updated.
Inverter firmware is being updated.
Monitor firmware is being updated.
LBS is abnormal.