Specifications And Technical Data; Conformity And Standards; Ups Environmental; Table 21 Environmental Requirements - Emerson Liebert EXM User Manual

60-100kva, 50/60hz
Hide thumbs Also See for Liebert EXM:
Table of Contents

Advertisement

8.0
S
PECIFICATIONS AND
8.1

Conformity and Standards

The Liebert eXM has been designed to conform to the following standards:
Harmonics
Electrical Fast Transient
Radiated Immunity
Conducted Immunity
Low-Frequency Signals
Transportation
The Liebert eXM has UL and c-UL approval.
8.2

UPS Environmental

The Liebert eXM is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Table 21
Environmental requirements
Acoustical Noise, dBA, at 55 in. (1.4m)
Operating Altitude
Relative Humidity
Operating Temperature, °F (°C)
UPS Storage/Transport Temperature, °F (°C)
Table 22
UPS mechanical characteristics
Rated Power, kVA
Dimensions, W x D x H, in (mm)
Weight, lb (kg)
Color
Protection Degree IEC (60529)
®
Liebert
eXM
T
ECHNICAL
Safety
UL 1778 4th Edition, CSA 22.2 107.3
Surge
IEC 61000-4-5 Criteria B
IEC 61000-3-4
IEC 61000-4-4, Criteria B
ESD
IEC 61000-4-2, Criteria B
FCC
Part 15, Class A
IEC 61000-4-3, Criteria A
IEC 61000-4-6, Criteria A
IEC 61000-2-2 Criteria A
ISTA Procedure 1H
ISO
9001
Misc
OSHA, ASME, NEMA PE-1
Item
23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000)
955 (433)
RAL 7021 (Black)
IP20
D
ATA
Requirements
59
3281 ft. (1000m) 1% maximum kW derate per 328 ft. (100m) rise
between 3281 and 9843 ft. (1000m and 3000m)
95%
104 (40)
-4 to 158 (-20 to 70)
60 - 100
66

Specifications and Technical Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents