Connecting An Actuator With Three Point Output - Viessmann VITOTRONIC 100 Installation And Service Instructions Manual

Type gc1 digital boiler control unit
Table of Contents

Advertisement

Installation
Connecting an actuator with three−point output
Use as:
H Butterfly valve
H Mixer motor
H Three−way mixing valve
M
1~
52
A1
| Open
~ Closed
68
Rated voltage:
Rated current:
Recommended
connecting
cable:
H05VV−F4G 0.75 mm
or
H05RN−F4G 0.75 mm
Run−time:
5 to 199 s,
adjustable via coding
address "40"
(delivered condition
125 s)
230 V~
max. 0.2 (0.1) A
2