Viessmann VITOTRONIC 100 Installation And Service Instructions Manual page 142

Type gc1 digital boiler control unit
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
Boiler/burner (cont.)
*1
04 :
Switching hysteresis
(Note see page 151)
Burner (mod.) (see page 103)
05 : 70
Burner curve
Boiler/burner
06 : 87
Maximum boiler water
temperature limit 87 ºC
Boiler
07 :
1
Consecutive boiler number
in multi−boiler systems
(in conjunction with coding
address "01")
Burner (two−stage/mod.) (see page 102)
*1
08 :
Maximum burner output
in kW
*1
The delivered condition is defaulted by the boiler coding card.
142
g y
Possible change
04 :
0
Switching hysteresis 4 K
Heat demand−dependent
switching hysteresis:
04 :
1
ERB50 function
(values from 6 to 12 K)
04 :
2
ERB80 function
(values from 6 to 20 K)
05 :
0
Linear burner curve
05 :
1
Non−linear burner
to
curve:
05 : 99
P
in kW
T
P
in kW
max
= P
in %
T
P
Partial output at
T
g of the actuator
operating time
P
Maximum output
max
06 : 20
Maximum boiler water
to
temperature limit
06 : 127
adjustable from 20 to
127 ºC
07 :
2
Consecutive boiler number
to
in multi−boiler systems
07 :
4
(in conjunction with coding
address "01")
08 :
0
Maximum output
to
adjustable from 0 to
08 : 199
199 kW;
1 step ¢ 1 kW
· 100 %