Code 2 - Viessmann VITOTRONIC 100 Installation And Service Instructions Manual

Type gc1 digital boiler control unit
Table of Contents

Advertisement

Code 2

Calling up code 2
1. Press L and G simultaneously
for approx. 2 s, until the first two
arrows appear in the display;
confirm with d.
Access to coding level 2.
2. Select the required coding address
with a or b,
the address flashes;
confirm with d,
the value flashes.
Overview
Coding in the delivered condition
System design
00 :
1
Boiler control without
DHW heating
System type
01 :
1
Single boiler system
Boiler/burner
02 :
1
Two−stage burner
03 :
0
Gas fired operation
g
g
p
3. Change the value with a or b;
confirm with d.
The value is saved and does not
flash for approx. 2 s. Then the
display flashes again. Further
addresses can now be selected
with a or b.
4. Press L and G simultaneously
for approx. 1 s.
Exit coding level 2.
Possible change
00 :
0
Set automatically, if "01 : 2" or
"01 : 3" has been programmed
00 :
2
Boiler control with DHW
heating
01 :
2
Multi−boiler system with
cascade control via LON BUS
(e.g. Vitotronic 333, type MW1)
01 :
3
Multi−boiler system with
cascade control via switching
contacts
(input aVD and aVH)
02 :
0
Single stage burner
02 :
2
Modulating burner
03 :
1
Oil fired operation (irreversible)
03 :
2
Set automatically, if an
incorrect boiler coding card is
inserted
Coding
141