Troubleshooting
Faults which are displayed at the programming unit
Fault
System
code
characteristics
Control mode
c4
Boiler cools down
c8
c9
ca
cb
118
Cause
Communication
with function
extension 0−10 V
faulty
Error
Low water indicator
Fault
Maximum pressure
limiter
Fault
Minimum pressure
limiter or
maximum pressure
limiter 2
Fault
Additional high
limit safety cut−out,
temperature limiter
or flue gas damper
(cont.)
Remedy
Check connections
and cables/leads; if
required replace
function extension
(see page 133).
Without function
extension,
set code "9d : 0"
Check water level in
system,
reset low water
indicator
(see page 136)
Check system
pressure, reset
maximum
pressure limiter
(see page 136)
Check system
pressure; reset
minimum or
maximum pressure
limiter (see page 136)
Check system
temperature; reset
high limit safety
cut−out or flue gas
damper
(see page 136)