Troubleshooting
Faults which are displayed at the programming unit
Fault
System
code
characteristics
Control mode
aa
Controlled
ab
operation, perhaps
DHW cylinder cold
Control mode
ac
ad
bC 0
116
Cause
Therm Control
configuration error
Plug aJA of
Therm Control
temperature sensor
not inserted
Cylinder storage
system
configuration error:
Code "55:3" has
been set, but
plug aJB is not
plugged in
and/or
Code "4C:1" and
"4E:1" have not
been set
Return temperature
raising
configuration error:
Code "0C:1" has
been set, but
plug aJA is not
plugged in
and/or
Code "4E:0" is not
set
Butterfly valve
configuration error:
Code "0C:2",
"0C:3" or "0C:4" is
set
and
Code "4E:1" is set
Short circuit
Flue gas
temperature sensor
(cont.)
Remedy
Insert plug aJA
Code "0d:0" must
be set for
Vitocrossal
Insert plug aJB
and check code
Insert plug aJA
and check code
With butterfly valve:
Code "4E:0" is set
Without butterfly
valve: Set code
"0C:0" or "0C:1"
Check flue gas
temperature sensor
(see page 132)