Code 2
(cont.)
Coding in the delivered condition
DHW
55 :
0
Cylinder heating,
hysteresis ± 2.5 K
56 :
0
Setting range for DHW
temperature 10 to 60 ºC
58 :
0
Without auxiliary function
for DHW heating
59 :
0
Cylinder heating:
Starting point 2.5 K K
Shutdown point + 2.5 K
5A :
0
No function
60 : 20
During DHW heating, boiler
water temperature is max.
20 K higher than set DHW
temperature
Possible change
55 :
1
Adaptive cylinder heating
active (speed of temp. rise
for cylinder temperature is
taken into account during
DHW heating)
55 :
2
Cylinder temperature
control with 2 cylinder
temperature sensors
55 :
3
Cylinder temperature
control
cylinder storage system
56 :
1
DHW temperature setting
range 10 to 95 ºC
Notes
H Observe the max.
permissible DHW
temperature
H Change control
thermostat "R"
58 :
1
Input of a second set DHW
to
value; adjustable from
1 to 95 ºC (observe coding
58 : 95
address "56" and section
"Additional function" on
page 124)
59 :
1
Starting point adjustable
to
from 1 to 10 K below the set
59 : 10
value
5A :
1 Flow temperature demand
of DHW cylinder is
maximum system value
60 : 10
The difference between the
to
boiler water temperature
60 : 50
and the set DHW
temperature is adjustable
from 10 to 50 K