Commissioning
Matching the coding addresses to the system version
Matching the control unit to a two−stage burner
1. Start up the burner.
2. Set the emissions test switch
to "h" (see page 127).
3. Determine the maximum burner
output through the fuel
consumption.
Record the relevant value.
4. Set the emissions test switch
to "a".
5. Press K and d simultaneously
for approx. 2 s.
Relay test is activated.
Address Setting of
08
Units and tens of the determined maximum output;
e.g. max. output: 225 kW select: 25
Values including 199 kW can be entered directly.
09
Hundreds of the determined maximum output;
e.g. set the max. output: 225 kW here: 2
0A
Relationship between base output and max. output in percent; e.g.
Base output: 135 kW
Max. output: 225 kW
135 kW
225 kW
102
@ 100 % + 60 %
6. Activate the "Burner stage 1 ON"
function with a (display: 1).
7. Determine the minimum burner
output (base load) through the
fuel consumption.
Record the relevant value.
8. Press d.
Relay test is completed.
9. Set the established values in code
2, see the table below and
page 142.
(cont.)