Type gc1 digital boiler control unit
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
Boiler/burner
23 :
0
No time interval for burner
maintenance
24 :
0
No maintenance display
Boiler/burner (two−stage)
Burner fuel consumption
26 :
0
(stage 1);
no count, if "26 :
"27 :
27 :
0
programmed
Boiler/burner
28 :
0
No burner interval ignition
Boiler/burner (two−stage)
Burner fuel consumption
29 :
0
(stage 2);
no count, if "29 :
"2A :
2A :
0
programmed
General
2b :
5
Maximum preheating time
of the butterfly valve
5 min
2C :
5
Maximum run−on time of
butterfly valve 5 min
*1
The fuel consumption can only be scanned in conjunction with Vitosoft or Vitocom.
,
0" and
0" have been
0" and
,
0" have been
p
g
Possible change
23 :
1
Adjustable time interval
to
from 1 to 24 months
23 : 24
24 :
1
Maintenance indication in
display (address is
automatically set and must
be manually reset after
maintenance)
26 :
1
Input of 0.1 to 9.9;
1 step ¢ 0.1 litres or
to
26 : 99
gallons/h
27 :
1
Input of 10 to 1 990;
1 step ¢ 10 litres or
to
27 : 199
gallons/h
28 :
1
The burner will be force−
started for 30 s after 5 h
29 :
1
Input of 0.1 to 9.9;
1 step ¢ 0.1 litres or
to
29 : 99
gallons/h
2A :
1
Input of 10 to 1 990;
1 step ¢ 10 litres or
to
2A : 199
gallons/h
2b :
0
No preheating time
2b :
1
Pre−heat time adjustable
to
from 1 to 60 min
2b : 60
2C :
0
No run−on time
2C :
1
Run−on time adjustable
to
from 1 to 60 min
2C : 60
Coding
*1
*1
*1
*1
145