Desa VH Series Stove"VICTOR HEARTH" Owner's Operation And Installation Manual page 14

Cast iron stove and b-vent (freestanding fireplace heater) burner system
Table of Contents

Advertisement

ventinG instaLLation
Continued
CHECKING VENT CAPACITY
Complete all gas piping, electrical, and vent
connections. After adjusting the burner system
and lighting the main burners, allow a couple of
minutes for warm-up. Hold a lighted match just
under the rim of the draft hood relief opening.
Proper venting will draw the flame toward or
into the draft hood. Improper venting, indicated
by escape or spillage of burned gas, will cause
match to flicker or go out. Smoke from a ciga-
rette will also be pulled into the draft hood if the
vent is drawing properly.
Figure 24 - Test for Proper Venting
CHIMNEYS
• Complete familiarity with chimney condi-
tion, height, size, clearance to combustibles
and other factors is essential.
NOTICE: Consult the authority
having jurisdiction in your area
regarding masonry chimney
venting applications.
NOTICE: A complete chimney
inspection by a qualified person
should be performed.
• Appliances using B-vent connectors to
vent into a masonry or factory-built chim-
ney should not exceed 1
for every inch of connector diameter (3"
vent connector has a maximum 4
length; 5" connector has maximum 7
foot length).
• Oversized chimneys should be relined with
appropriate listed relining systems.
• Clean out access may be required.
14
/
feet in length
1
2
/
foot
1
2
/
1
2
www.desatech.com
RELINING SYSTEMS
• Suitability and approval of relining materials
should be determined.
• Condition, size, height, and termination
of the chimney to be relined must be
determined.
• No substitution of components should be
made.
• Joints and connectors should be made
according to manufacturer's instructions.
NOTICE: Consult the authority
having jurisdiction in your area
regarding listed chimney liner
venting applications.
WARNING: Operation of
improperly installed and main-
tained venting system could
result in serious injury, property
damage, or loss of life.
Figure 25 - Straight Installation into
Masonry Chimney
112127-01C