On terminals J3 or J4 connector 6 of the following 28 signals can be selected from the display
(access only with password): MENU / PARAMETER MENU / LEVEL 2: SERVICE.
0 - No signal
1 - Buzzer
2 - General alarm (NO)
3 - Load on mains
4 - Stop operation
5 - Load on inverter
6 - Mains failure
7 - DC overvoltage
8 - Low battery
9 - Overload
10 - Overtemperature
11 - Inverter-mains not syncrony
12 - Bypass locked
13 - Bypass mains failure
14 - Rectifier mains failure
Programmable functions on input contacts (X1 - J2)
Some UPS functions can be activated by parameters (access with password only) when an
external NO contact is closed on:
No function
Inverter OFF
Print all
Voltage free contacts:
Gen Set signalling
If an Emergency generator set supplies the UPS in case of utility failure and the generator is
particularly unstable in frequency, it should be suitable to install the signal "generator on" on
terminals X1 / 11, 22 (Normally Open voltage-free contact) or on connector J2 / 11, 24 (see Fig.
10.2.1-1 / X1 and J2).
When this contact closes, it causes the change of certain settable functions such as:
Enabling or disabling of synchronisation and consequently the load transfer to generator.
The battery recharge inhibition during the generator operation, or after what delay from
generator start the battery will start to be recharged.
Consult your nearest Service Centre for more information.
OPM_LPS_33E_10K_30K_4CN_V010.doc
Output signals on voltage-free contacts
Max. DC / AC: 24V / 1.25A
IEC 950 (SELV circuit)
Min. signal level: 5VDC / 50mA
76/82
15 - Battery discharge
16 - Manual bypass ON
17 - Rectifier ON
18 - Inverter ON
19 - Battery boostcharge
20 - Battery earth fault
21 - Battery fault
22 - Relay input 1
23 - Relay input 2
24 - Relay output ON
25 - Relay output OFF
26 - EPO (Emergency Power Off)
27 - IEM Mode ON
28 - General alarm (NC)
Inverter On
Generator ON
Status relay
Operating Manual LP 33 / 10-20-30 kVA
GE