GE Digital Energy LP 33 Operating Manual page 77

10 – 20 – 30 kva series 4
Hide thumbs Also See for Digital Energy LP 33:
Table of Contents

Advertisement

g
EPO (Emergency Power Off)
An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on
terminals X2 / 1, 2 or connector J2 / 12, 25 of the Customer Interface (see Fig. 10.2.1-1 / X2 & J2).
Fig. 10.2.1-2 PCB Customer Interface
To enable this function, remove jumper JP3 on the Customer Interface and
the cable on the terminal X2 / 1, 2 (see Fig. 10.2.1-2).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP8 on the control
board P2 – Mainboard are OFF (see Fig. 10.2.1-3).
In a parallel system a separate NC (Normally Closed) contact must be connected
individually to each unit.
When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter;
and the contactors K4, K6 and K7.
When the EPO has been activated, the system must be restored as following:
Press the push-button EPO (contact on X2/1, 2 is closed again).
Perform the command INVERTER OFF entering the screen:
MENU/COMMAND MENU/INVERTER OFF.
Start the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON.
OPM_LPS_33E_10K_30K_4CN_V010.doc
J2
JP3
X2
X1
NOTE !
This procedure could imply a load shutdown.
77/82
P2 - Mainboard
J28
JP8
Fig. 10.2.1-3 PCB P2 - Mainboard
INVERTER ON
>
INVERTER OFF ‫٭‬
>
INVERTER ON
INVERTER OFF
Operating Manual LP 33 / 10-20-30 kVA
GE
X7
1
2
‫٭‬