g
Rectifier
U1=228V
U2=230V
U3=229V
Rectifier frequency
f=50.0Hz
Inverter
U1=230V
U2=230V
U3=230V
Inverter frequency
f=50.0Hz
Inverter status
f=50.0Hz
Inverter status
Synchronized
Load on Phase 1
U=230V
I=14A
Load on Phase 2
U=230V
I=14A
Load on Phase 3
U=230V
I=14A
Battery Temperature
+25°C
UPS Operating Time
450h
INV Operating Time
430h
Minor Mains Faults
100
Major Mains Faults
150
Overloads
30
OPM_LPS_33E_10K_30K_4CN_V010.doc
1. Rectifier input voltage information screen and rectifier input
line voltage L1 phase.
2.
RECTIFIER INPUT LINE VOLTAGE L2 AND L3
PHASES.
1. Rectifier input frequency information screen.
2.
RECTIFIER INPUT FREQUENCY.
1. Inverter output voltage information screen and inverter
output line voltage L1 phase.
2.
INVERTER OUTPUT LINE VOLTAGE L2 AND L3
PHASES.
1. Inverter output frequency information screen.
2. Inverter output frequency.
1. Inverter output frequency information screen.
2.
INVERTER OUTPUT FREQUENCY.
1. Inverter status information scree.
2.
SYNCHRONISATION
RESPECT TO MAINS.
1. Load on output phase L1 information screen.
2.
VOLTAGE, CURRENT AND LOAD PERCENTAGE
50%
PHASE L1.
1. Load on output phase L2 information screen.
2.
VOLTAGE, CURRENT AND LOAD PERCENTAGE
50%
PHASE L1.
1. Load on output phase L3 information screen.
2.
VOLTAGE, CURRENT AND LOAD PERCENTAGE
50%
PHASE L1.
1. Battery temperature information screen.
2.
BATTERY TEMPERATURE.
1. Operation time UPS information screen.
2.
OPERATING TIME (CPU POWERED) FOR THE UPS
(HOURS).
1. Operation time inverter information screen.
2.
OPERATING TIME WITH INVERTER SUPPLYING THE
LOAD (HOURS).
1. Screen informing about the quality of the input power.
2.
THE QUANTITY OF BYPASS MAINS OUT OF
TOLERANCE FAULTS.
1. Screen informing about the quality of the input power.
2.
THE QUANTITY OF RECTIFIER MAINS OUT OF
TOLERANCE FAULTS.
1. Screen informing about the quality of the output power.
2.
THE TOTAL NUMBER OF DETECTED OUTPUT
OVERLOADS.
STATUS