3.3 S
etup
3.3.1 Foundation
Provide a firm, level foundation, preferably of concrete. Lifting the front of the boiler slightly will allow the boiler
to be rolled off the shipping skid onto the concrete foundation. Once in position, the wheel bolts may be removed
allowing the wheels to recess up into the boiler. The base will sit flat on the provided foundation. If the boiler is
to be pulled out for maintenance, the wheels may be left attached.
3.3.2 Placement
The boiler must be level to function properly. Six 9/16" holes in the base may be used for 3/8" anchor bolts.
 
3.3.3 Clearances
If the boiler is to be installed near combustible surfaces, the minimum clearances shown in Table 3.3.3 and
Figure 3.3.3. must be maintained. Failure to provide for the service access clearances, even with non-
combustible surfaces, may cause future problems servicing the boiler. Maintain a clearance from the vent to
combustible surfaces of 24" or as specified in the vent manufacturer's listed installation instructions. The boiler
must be installed in a space large enough in comparison to the boiler as described in the National Fuel Gas
Code, ANSI Z223.1, latest edition.
Table 3.3.3
 
Type of Surface
 
 
 
Combustible Surfaces Minimum Clearances
 
 
Recommended Clearances for Service Access
 
Figure 3.3.3
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
* "B" Clearance depends upon exhaust vent configuration.
† "C" Space required for pipes, ducts, etc. in this area above the boiler.
** Do not put pipes, ducts, vents, etc in this space. Electrical conduit must be installed
vertically so that the side doors can be opened.
NOTE: Annual maintenance items can be accessed from the front of the boiler.
 
Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351
Dimensions (inches)
A
B
C
30
12*
24†
30
12*
24†
12
Gas Fired Boiler
D
12**
12**