Recommended mounting plate retention spots and
dimensions
Recommended mounting plate
Place a leveler
retention spots (5 spots in all)
on raised tab.
120.5
203
41.3
54.5
160
50
330.5
Keep here the piece cut out
from the unit for piping
* The removed pipe port cover can be
kept in the mounting plate pocket.
2.Boring a wall hole and installing wall embedded pipe
1.Make the piping hole (
slant to the outdoor side.
2.Insert the piping-hole sleeve into the hole to prevent the con-
nection piping and wiring from being damaged when passing
through the hole.
Indoor
Wall pipe
3.Flarig woke and connection of piping
3.1 Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in theflaring
work. Carry out correct flaring work using the follow-ing procedure.
Cut the pipes and the cable
1. Use the piping kit accessory or pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than the measured distance.
4. Cut the cable 1.5m longer than the pipe length.
Copper
pipe
90
Use tape measure
as shown.
Position the end of
a tape measure at .
103
245.5
160
54
Gas pipe end
331
Liquid pipe end
770
Drain hose
position
Removed pipe
port cover
Mounting plate
A
55) in the wall at a slight downward
Φ
Outdoor
Seal pad
Φ
55
Slanted Uneven Rough
Burr removal
1.Completely remove all burrs from the cut cross section of
pipe/tube.
2. Put the end of the copper tube/pipe in a downward direc-
tion as you remove burrs in order to avoid dropping burrs
into the tubing.
41.3
Through-
the-wall
hole Φ 55mm
Unit: mm
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then
put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in
the table above.
Carry out flaring work using flaring tool as shown below.
Check
1.Compare the flared work with figure below.
2.If flare is noted to be defective, cut off the flared section and re-
flare it.
Pipe
Reame r
Point down
Flare nut
Copper tube
Bar
Bar
Copper pipe
Clamp handle
Outside diameter
mm
inch
Φ6.35
1/4
Φ9.52
3/8
Φ12.7
1/2
Φ15.88
5/8
Φ19.05
3/4
Smooth all round
Inside is shiny without scratches
= Improper flaring =
Inclined
Surface
damaged
Even length
all round
Handle
Yoke
Cone
Red arrow mark
A
mm
0~0.5
0~0.5
0~0.5
0~1.0
1.0~1.3
Cracked Uneven
thickness