3.2
Field Refrigerant Piping
3.2.1 Heat Pump Series
1. The following materials should be used for all refrigerant piping.
Materials: Deoxidized phosphorous seamless copper pipe or equivalent
2. The tips for insulation
Both Gas, Liquid piping must be insulated.
Materials: Glass fiber or heat resistant polyethylene foam.
Thickness: 1/2 inch or more
Insulation of both liquid and gas pipe
3.2.2 Heat Recovery Series
Suction, Discharge Gas piping, liquid piping must be insulated.
Example of thermal insulation work.
3 piping section (between outdoor unit and Branch Selector
unit)
Installation of Outdoor Units
2 piping section (between Branch Selector unit and indoor
unit)
REFNET Pipe System