Dxv45 Dt3 Features - Quick Reference Information; Initial Startup Advice - Mendota DT3-PF2-LX Operating Instructions Manual

Gas direct vent fireplace with premium fiber log set combustion system
Table of Contents

Advertisement

DXV45 DT3 FEATURES - QUICK REFERENCE INFORMATION

EXTERNAL DIMENSIONS: 40-3/8" Wide X 39" High X 19-1/8" Deep
MINIMUM FRAMING DIMENSIONS: 41" WIDE x 38-1/8" HIGH X 20" DEEP
2
GLASS SIZE: NeoCeram Glass with non-reflective coating. Visible Glass measures 707.5 in
. Actual Glass size is 840
2
in
.
MANTEL ALLOWANCE: 8" Deep Mantel at 14" Above Top Convection Opening
VENT SYSTEM ALLOWANCE: Top Vent Only. 0" Vertical 24" max horizontal. 55 feet Vertical Maximum. 5" exhaust and
8" combustion air intake coaxial vent pipe required. 12' maximum horizontal run allowed with 4' minimum vertical starter
section.
VENT DAMPER ADJUSTMENT AVAILABLE: There is one exhaust vent damper included in this unit and located in the
top convection chamber at the center.
CONTROLS: IPI Electronic Ignition System with AC Primary Power and DC Backup Power. Accent light and Blowers op-
erate on AC Power only. Thermostatic Remote Control Transmitter with Smart Thermostat Mode.
BLOWER SYSTEM: 210 CFM Dual Blower System. 120VAC, 2Amps. Dedicated Hot Power only. No switches, Fan Speed
Controls or Light Dimmers are allowed in same circuit. Blower speeds can be varied from Remote Control. Fan cannot be
turned completely off.
Accent Light System: Accent Light System Included. Light can be turned on or off or dimmed using dimmer mounted
behind lower grill. Accent Light can also be turned on or off and dimmed using Remote Control Transmitter.
BURNER SYSTEM: Dual 304 Stainless Steel Tubular burners.
BURNER AIR SHUTTER SYSTEMS: Externally controllable Rear Burner air shutter and Internal rotary Front Burner air
shutter.
LOG SET: 10-piece, Premium Fiber Log Set with Real- Glow effects and Real ember bed.
REFRACTORY PANELS: High Detail Red Clinker Soldier Course Fiber Brick Panels included. Brick Panels required for
operation.
NATURAL GAS INFORMATION: Factory equipped for Natural Gas. 4.5"WC Minimum inlet pressure required. For NG
applications, Front Burner Orifice Size is #44 and the Rear Burner Orifice Size is #38.
LPG INFORMATION: An LP conversion kit is required to burn LPG in this appliance. Use kit #HA-42-00302 to convert
this appliance to burn LPG. 12"WC Minimum inlet pressure required. For the DXV45 DT3 LPG application, Front and
Rear orifices are to be #53 (Rear) and 3/64" (Front). For higher altitude, adjustment to orifice size may be necessary.

INITIAL STARTUP ADVICE

PAINT CURING CYCLE RECOMMENDATION: It is recommended that you run this Fireplace on maximum flame height,
for 3 cycles of 2 hours ON and 2 hours OFF, initially, to cure the paint. Some non-toxic smoking will be visible during the
cure cycles. It is recommended that all windows be opened during the first 2-hour burn cycle to expel the visible smoke.
BLOWER BREAK-IN PERIOD: The integrated blowers in this Insert may exhibit some bearing noise and electrical static
noise during the first few days of operation. This is normal during the break-in period. It is recommended that following the
Paint Curing Cycle, the blowers be run at their maximum speed for two 3-hour periods. The burner flames must be on dur-
ing these cycles. The blowers in a few fireplaces may take longer to break-in and may require additional operation time
before all extraneous noise is eliminated. Please allow adequate operational time for the blowers to break-in before you
contact your dealer for service.