Should the real percentage of the worst possible case be below that set (except the neutral zone), the
formula used for the new set-point is:
Set
Set
%
new
old
%
(calculated percentage value) - (percentage set for the worst possible case)
RLS
release-gain parameter value
gain
And vice-versa, should it be above the set percentage (except the neutral zone), the formula used for the
new set-point is:
Set
Set
%
new
old
%
(calculated percentage value) - (percentage set for the worst possible case)
CALL
call-gain parameter value
gain
The calculated percentage refers to the analysis range and it changes from time to time based on the real
system conditions.
Each engine must be activated by pressing enable system. To deactivate it, press disable system.
The engine status is displayed at the top of the window.
CRO results with graphs
To display the status of the three worst utilities, from the cold call point of view, open the menu
OperationView Data.
Select the class and then the devices for which the report is to be issued. The three devices considered to
be the worst in the latest period, will be shown on the screen (as illustrated by the image below). The worst
device is that indicated in the red column.
1592010880 XWEB3000_5000 EVO OPR GB r1.0 2014.11.28
RLS
 
 
gain
1000
CALL
 
 
gain
1000
-
56/100