Some parameters must be set for each "Setting":
-
Setting Name: identifies the notification level
-
{166Notify on Start167}: enabled for the sending of new alarm notifications
-
Notify on End: enabled for the sending of alarm-over notifications
-
Send Single Notification: the enabling of this parameter invalidates the accumulation time. If the
system detects two alarms simultaneously, the users will receive two separate notifications.
-
Accumulation Time: the time during which the system awaits the detection of new alarms for the
sending of a cumulative notification
-
Re-send Time: interval between notifications of persisting alarms. For example, if a new alarm message
is sent but ignored or lost, the system notifies the same message again after the indicated time. This
parameter is critical to "level" climb logic: if this parameter value is 0 after the first notification, the level is
scaled upwards
-
Resend TTL: maximum time within which the continuously active alarm is notified of the current level
rules. After this time, the level is up-scaled to the next level indicated in the alarm-category.
-
Service Activation:
1. AUX2/AUX3: the alarm notification occurs by means of the local relay, physically present on rear
of the XWEB-EVO machine. The configuration parameters of this relay are available on page
"MenuXWEB SYSTEM SETUPSystem SetupAUX Outputs"
2. RAUX1/ RAUX2/ RAUX3/RAUX4: the alarm notification occurs by means of the remote relay
physically present on an XJR40D controller connected to the Modbus network. The relay
parameters of this controller are available on page "MenuXWEB SYSTEM SETUPSystem
SetupAUX Outputs"
3. PRINTER: the alarm notification occurs by means of the local printer physically
connected/configured to the XWEB-EVO. The configuration parameters of this printer are
available on page "MenuXWEB SYSTEM SETUPSystem SetupPrinters"
4. XCENTER: the alarm notification is sent to the Dixell XCenter system. Configure the system by
accessing the page "MenuXWEB SYSTEM SETUPSystem SetupXCenter"
5. FAX: the alarm notification is performed through means of a fax message being sent over the
telephone line
6. FAX OCR: the alarm notification is performed by means of a fax message being sent over the
telephone line in a fixed-width font format and therefore automatically segmented
7. EMAIL: the alarm notification is performed by means of an email message being sent as
demonstrated below