time periods. If the ramp time is set to 0, there will be an immediate step transition in
the set points from the previous time window. If the ramp time is not 0, for example, if
it is 30 minutes, then the setpoints will adjust gradually from one time period to the next
over the 30 minute time span.
1.1.1.5.2.
This is sometimes called "hysteresis band". For cooling, it is the number of degrees
the temperature needs to drop from the lower boundary of its current stage before it
switches to the lower stage. (Note: without deadbands, equipment tends to cycle fre-
quently and constantly change stages when the temperature reaches the setpoint or a
stage boundary). For heating, it is the number of degrees the temperature needs to rise
above the temperature boundary before it switches to a lower heating stage.
Typical values will be 1 to 2 degrees, Fahrenheit.
1.1.2.
1.1.2.1.
By selecting the On option, you will be able to program separate setpoints and other
parameters for your defined night time period. The Off option disables this second set
of setpoint parameters.
1.1.2.2.
Same description as for Day
1.1.2.3.
Same description as for Day
1.1.2.4.
Same description as for Day
1.1.2.5.
1.1.2.5.1.
The Night Start Time is the time when the night setpoints are engaged.
1.1.2.5.1.1.
Same description as for Day
iGrow Series 100 Manual
DeadBand
Set – NIGHT
On / Off
SetHeat Setpoint
SetCool Setpoint
Set Stage Separation
Set Time
Set NIGHT Start Time
Sun Based or Absolute
89