4.3 Front Panel Settings

Listed below are the default settings of the primary UPS parameters.
Settings
1) O/P VOLT SET
100V/110V/115V/120V/127V
(Output Voltage Set)
208/220/230/240 Vac
2) I/P FREQ SET
±2%
(Input Frequency Set)
±5%
±7%
3) I/P BYPASS SET
±10%
(Input Bypass Setting)
+10% -15%
+15/-20%
4) FREE RUN SET
ON / OFF
5) HE MODE SET
ON / OFF
6) MANUAL BYPASS
ON / OFF
Options
Default
120V
230V
±5%
+10/-15%
ON
OFF
OFF
16
Remarks
120V (FOR LV series)
230V (FOR HV series)
Input Frequency range
in Free Run mode.
Input Voltage range when
Bypass mode is on.
If ON, enable UPS runs on
unsynchronized Mode.
For example, if input
frequency 55Hz, output
frequency will stay at 60Hz.
If OFF, disable UPS runs on
unsynchronized mode.
For example, if input
frequency 55Hz, UPS will go
to Battery mode.
If ON, enable UPS runs on
high efficiency mode.
Bypass mode is on when
power flows at 95% or lower.
If OFF, disable UPS runs on
high efficiency mode.
Bypass mode is on when
power flows at 85% or lower.
If ON, enable UPS switch to
Bypass mode immediately.