4.4

Front Panel Settings

Listed below are the default settings of the primary UPS parameters.
Settings
1) O/P VOLT SET
100V/110V/115V/120V/127V
(output voltage
208/220/230/240 Vac
set)
2) I/P FREQ SET
+/- 2%
(input frequency
+/- 5%
setting)
+/- 7%
3) I/P BYPASS
+/- 10%
SET
+10% -15%
(input bypass
+15% -20%
setting)
4) FREE RUN
ON/OFF
SET
5) HE MODE SET
ON/OFF
6) MANUAL
ON/OFF
BYPASS
Options
Default
120V
230V
+/- 5%
+10%
-15%
ON
OFF
OFF
12
Remarks
120V (FOR LV series)
230V (FOR HV series)
Input Frequency range in
Free Run mode
Input Voltage range when
Bypass mode is on
If ON, enable UPS runs on
Asynchronous mode.
For example:
If input freq 55Hz
output freq stays at 60Hz.
If OFF, disable UPS runs on
synchronous mode.
For example:
If input freq 55Hz,
UPS will go to battery mode.
If ON, enable UPS runs in
High efficiency mode. The
unit will be in bypass mode
with 95% or higher
efficiency.
If OFF, the unit will be in the
online mode with 85%
efficiency.
If ON, enable UPS switch to
Bypass mode immediately.