Rear Vent Configuration with Horizontal Termination (no vertical rise)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
and diffuser positions.
HINT: Travis Industries provides a minimum rear vent kit (sku 98900168). It includes a 4" section and
a horiztontal termination cap.
Vent with No 45° Elbow
3 feet
0 feet
Vent with 1 45° Elbow
3 feet
0 feet
See the charts above to
determine maximum vent
Optional 45° Elbow
© Travis Industries
Installation
(for qualified installers only)
EXHAUST RESTRICTOR REMOVAL
Termination
• Exhaust Restrictor Removed
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)
• Min. 4" Horizontal Section
• Max.48" Horizontal Section(s)
• Exhaust Restrictor Removed
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)
• Min. 4" Horizontal Section
• Max. 24" Horizontal Section(s)
4080214
If venting to the rear with no vertical
sections, remove and discard the exhaust
restrictor. Replace the screws in the same
holes.
100-01182_003