Control circuit specifications
2.3.3

Control circuit terminal layout

(1) Common terminals of the control circuit (SD, 5, SE)
Terminals SD, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each other. Do not
earth(ground) these terminals.
Avoid connecting the terminal SD and 5 and the terminal SE and 5.
Terminal SD is a common terminal for the contact input terminals (STF, STR, STOP, RH, RM, RL, JOG, RT, MRS, RES,
AU, CS).
The open collector circuit is isolated from the internal control circuit by photocoupler.
Terminal 5 is a common terminal for frequency setting signal (terminal 2, 1 or 4), analog current output terminal (CA)
and analog output terminal AM.
It should be protected from external noise using a shielded or twisted cable.
Terminal SE is a common terminal for the open collector output terminal (RUN, SU, OL, IPF, FU).
The contact input circuit is isolated from the internal control circuit by photocoupler.
(2) Signal inputs by contactless switches
The contacted input terminals of the inverter (STF, STR, STOP,
RH, RM, RL, JOG, RT, MRS, RES, AU, CS) can be controlled
using a transistor instead of a contacted switch as shown on the
right.
32
A1
B1
C1
A2
B2
RL
RM
RH
RT
AU
SE
RUN
SU
IPF
OL
FU
C2 10E 10
2
5
STOP
MRS
RES
SD
CA
AM
SD
SD
STF
STR
JOG
External signal input using transistor
Control circuit terminal
4
Terminal screw size: M3.5
Tightening torque: 1.2N.m
1
CS
PC
+24V
STF, etc
Inverter
SD