Connection Of The Power Regeneration Common Converter (Fr-Cv)(Fr-F720-02330 (Fr-F740- 01160) Or Less) - Mitsubishi Electric FR-F720-00046 Instruction Manual

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

Connection of stand-alone option units
2.4.5
Connection of the power regeneration common converter (FR-CV)(FR-F720-
02330 (FR-F740-01160) or less)
When connecting the power regeneration common converter (FR-CV), make connection so that the inverter terminals
(P/+, N/-) and the terminal symbols of the power regeneration common converter (FR-CV) are the same.
After making sure that the wiring is correct, set "2" in Pr. 30 Regenerative function selection. (Refer to page 108.)
MCCB
Three-phase
AC power
supply
*1
Remove the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 of the inverter, and connect the
control circuit power supply across terminals R1/L11-S1/L21. Always keep the power input terminals R/
L1, S/L2, T/L3 open. Incorrect connection will damage the inverter. (E.OPT (option fault) will occur. (Refer
to page 282.))
Do not insert an MCCB between the terminals P/+ − N/- (between P/L+ − P/+, between N/L- − N/-).
*2
Opposite polarity of terminals N/-, P/+ will damage the inverter.
*3
Assign the terminal for X10 signal using any of Pr. 178 to Pr. 189 (input terminal function selection).
(Refer to page 116)
*4
Be sure to connect the power supply and terminals R/L11, S/L21, T/MC1.
Operating the inverter without connecting them will damage the power regeneration common converter.
*5
Be sure to connect terminal RDYB of the FR-CV to the X10 signal or MRS signal assigned terminal of the
inverter, and connect terminal SE of the FR-CV to terminal SD of the inverter. Without proper connecting,
FR-CV will be damaged.
CAUTION
⋅ The voltage phases of terminals R/L
⋅ Use sink logic (initial setting) when the FR-CV is connected. The FR-CV cannot be connected when source logic is
selected.
⋅ Do not remove a jumper across terminal P/+ and P1.
42
Dedicated stand-alone
reactor (FR-CVL)
MC1
R/L11
R2/L12
S/L21
S2/L22
T/L31
T2/L32
, S/L
, T/MC1 and terminals R2/L
11
21
FR-CV type
Power regeneration
common converter
R2/L1
S2/L2
P/L+
T2/L3
N/L−
P24
R/L11
SD
S/L21
*4
RDYA
T/MC1
*5
RDYB
RSO
SE
, S2/L
, T2/L
must be matched.
1
2
3
R/L1
U
S/L2
*1
V
IM
T/L3
W
R1/L11
S1/L21
Inverter
P/+
*2
N/−
PC
SD
X10
*3
RES

Hide quick links: