(5) Selection of command source in Network operation mode (Pr. 338, Pr. 339)
There are two control sources: operation command source, which controls the signals related to the inverter start
command and function selection, and speed command source, which controls signals related to frequency setting.
⋅ In Network operation mode, the commands from the external terminals and communication (RS-485 terminals or
communication option) are as listed below.
Operation
Pr. 338 Communication operation command source
Location
Pr. 339 Communication speed command source 0: NET
Selection
Running frequency from communication
Fixed function
Terminal 2
(Terminal-
equivalent
Terminal 4
function)
Terminal 1
Low speed operation command/
0
RL
remote setting clear
Middle-speed operation command/
1
RM
remote setting deceleration
High speed operation command/
2
RH
remote setting acceleration
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG Jog operation selection
Selection of automatic restart after
6
CS
instantaneous power failure
7
OH
External thermal relay input
8
REX Fifteen speed selection
10
X10
Inverter operation enable signal
FR-HC or MT-HC connection,
11
X11
instantaneous power failure detection
12
X12
PU operation external interlock
External DC injection brake
13
X13
operation is started
14
X14
PID control valid terminal
16
X16
PU-external operation switchover
Output stop
24
MRS
PU operation interlock
25
STOP Start self-holding selection
60
STF Forward rotation command
61
STR Reverse rotation command
62
RES Reset
63
PTC PTC thermistor input
64
X64
PID forward action switchover
65
X65
PU-NET operation switchover
66
X66
External-NET operation switchover
67
X67
Command source switchover
70
X70
DC feeding operation permission
71
X71
DC feeding cancel
72
X72
PID integral value reset
[Explanation of table]
External
: Command only from control terminal signal is valid.
NET
: Command only from communication is valid
Combined
: Command from either of external terminal and communication is valid.
: Command from either of external terminal and communication is invalid.
Compensation : Command by signal from external terminal is only valid when Pr. 28 Multi-speed input compensation selection = "1"
REMARKS
⋅ The command source of communication is as set in Pr. 550 and Pr. 551.
⋅ The Pr. 338 and Pr. 339 settings can be changed while the inverter is running when Pr. 77 = "2". Note that the setting change is
reflected after the inverter has stopped. Until the inverter has stopped, communication operation command source and
communication speed command source before the setting change are valid.
Selection of operation mode and
0: NET
1:External 2:External 0: NET
NET
NET
NET
External
External
Compensation
NET
External
NET
NET
External
NET
NET
External
NET
NET
Combined
External
External
NET
External
NET
External
External
External
NET
NET
External
NET
External
Combined
External
NET
NET
External
External
NET
External
NET
External
External
External
NET
NET
NET
External
NET
operation location
1: External
Remarks
1:External 2:External
NET
External
External
External
Pr. 59 = "0" (multi-
speeds)
External
Pr. 59 = "1 , 2"
(remote)
External
External
Combined
External
Pr. 59 = "0"
External
(multi-speeds)
External
External
External
Pr. 79
Pr. 79 = "7"
When X12 signal
is not assigned
External
External
External
External
External
External
External
"7"
4
193