Mitsubishi Electric FR-F720-00046 Instruction Manual page 260

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

· When using two motors in the alternative-direct system (Pr. 579 = "3")
RIO1
RIO2
RO1
RO2
Pr. 125
Pr. 584
Speed of
motor 1(M1)
Inverter
operation
Speed of
motor 2(M2)
CAUTION
· If the start signal is turned off during operation, the inverter-driven motor is decelerated to stop, and the motors under
commercial power supply operation are switched over to inverter-driven operation one at a time and decelerated to a stop
after frequency search in order from the longest operation time.
· When an error occurs while running, MC (RO1 to RO4) turns off and the inverter output is shut off.
· If the MRS signal is turned on during operation, the inverter-driven motor is shut off. Although the motor with the longest
operating time of the commercial power supply operation is switched to the inverter operation after elapse of time set in Pr.
591 Auxiliary motor stop detection time , the motor remains in the output shut off status. Frequency search is made after the
MRS signal turns off and inverter operation is started.
· If the starting signal is turned on during deceleration to stop regardless of the Pr. 579 setting, operation by the advanced PID
control is performed again at the point when the signal is turned on.
♦ Parameters referred to ♦
Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments
Pr. 127 to Pr. 134, C42 to C45 (PID control)
Pr.178 to Pr.189 (input terminal function selection)
Pr. 190 to Pr. 196 (output terminal function selection)
Pr. 580
Pr. 580
Pr. 581
Pr. 590
Commercial
Motor
Motor
power
coasting
coasting
supply
operation
Pr. 581
Pr. 591
Pr. 587
Inverter
Pr. 902
operation
Refer to page 225
Refer to page 116
Refer to page 122
Special operation and frequency control
Pr. 57 + Pr. 58
Pr. 577
Pr. 590
sleep
Pr. 584
coasting
Inverter
operation
The motor is
The starting motor is
inverter-driven
switched over from M1
after frequency
to M2 after sleep.
search.
Refer to page 96
Pr. 581
Pr. 580
Motor
Commercial
power
supply
operation
251