Main circuit terminal specifications
• FR-F720-00630 (FR-F740-00310) or more
1) Remove the upper screws.
2) Remove the lower screws.
3) Pull the jumper toward you to
remove.
4) Connect the separate power supply
cable for the control circuit to the
upper terminals (R1/L11, S1/L21).
CAUTION
· Be sure to use the inverter with the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 removed when supplying power
from other sources. The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the
primary side of the MC.
· The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs according to the inverter
capacity.
200V class
400V class
· If the main circuit power is switched off (for 0.1s or more) then on again, the inverter resets and a fault output will not be held.
26
R1/
L11
R/L1S/L2 T/L3
MC
Main power supply
Power supply
terminal block for
the control circuit
FR-F720-00630 or less
60VA
FR-F740-00310 or less
60VA
S1/
L21 Power supply
terminal block
for the control circuit
FR-F720-00770 to 01250
FR-F720-00630
FR-F740-00470, 00620
FR-F740-00310, 00380
FR-F720-00770
FR-F720-00930 or more
80VA
FR-F740-00380
FR-F740-00470 or more
60VA
3)
Power supply terminal block
for the control circuit
R1/L11
S1/L21
1)
2)
4)
FR-F720-01540 or more
FR-F740-00770 or more
U
V
80VA
80VA
W