Mitsubishi Electric FR-F720-00046 Instruction Manual page 133

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

Function assignment of external
terminal and control
Setting
Signal
Positive
Negative
Name
Logic
Logic
91
191
Y91
92
192
Y92
93
193
Y93
94
194
ALM2
95
195
Y95
96
196
REM
98
198
LF
99
199
ALM
9999
*1
Note that when the frequency setting is varied using an analog signal or
frequency) signal may alternate on and off depending on that varying speed and the timing of the varying speed due to acceleration/
deceleration time setting. (The output will not alternate on and off when the acceleration/deceleration time setting is "0s".)
*2
When a power supply reset is performed, the fault output 2 signal (ALM2) turns off as soon as the power supply switches off.
REMARKS
⋅ The same function may be set to more than one terminal.
⋅ When the function is executed, the terminal conducts at the setting of any of "0" to "99", and does not conduct at the setting of
any of "100" to "199".
⋅ When Pr. 76 Fault code output selection = "1", the output signals of the terminals SU, IPF, OL and FU are switched as set in Pr. 76.
(When an inverter fault occurs, the signal output is switched to the fault code output.)
⋅ The output assignment of the terminal RUN and fault output relay are as set above regardless of Pr. 76.
CAUTION
⋅ Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection) may affect the other functions.
Please make setting after confirming the function of each terminal.
⋅ Do not assign signals which repeat frequent ON/OFF to A1, B1, C1, A2, B2, C2. Otherwise, the life of the relay contact decreases.
(2) Inverter operation ready signal (RY signal) and inverter running signal (RUN, RUN3 signal)
Power
ON
supply
ON
STF
RH
Pr. 13
Starting
frequency
Reset
processing
ON
RY
RUN
ON
RUN3
124
Function
Output when a fault occurs due to the
Fault output 3
internal circuit failure of inverter wiring
(power-off signal)
mistake.
Turned on and off alternately every time the
Power saving
power saving average value is updated
average value
when the power saving monitor is used.
updated timing
Cannot be set to Pr. 195 and Pr. 196 (relay
output terminal).
Average current value and maintenance
Current average
timer value are output as pulses.
value monitor signal
Cannot be set to Pr. 195 and Pr. 196 (relay
output terminal).
Output when the fault occurs. Continues
outputting the signal during inverter reset
Fault output 2
and stops outputting after reset is cancelled.
*2
Maintenance timer
Output when Pr. 503 rises to or above the Pr.
signal
504 setting.
Output to the terminal when a value is set to
Remote output
the parameter.
Output when an alarm (fan failure or
Alarm output
communication error warning) occurs.
Output when the fault occurs. The signal
Fault output
output is stopped when the fault is reset.
No function
OFF
OFF
ON
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
ON
OFF
OFF
Operation
of the operation panel (FR-DU07), the output of the SU (up to
⋅ When the inverter is ready to operate, the output of the operation
ready signal (RY) is on. It is also on during inverter running.
⋅ When the output frequency of the inverter rises to or above
Pr. 13 Starting frequency, the output of the inverter running
signal (RUN) is turned on. During an inverter stop or DC
injection brake operation, the output is off.
⋅ The output of the RUN3 signal is on when the inverter running
and start signals are on.
(For the RUN3 signal, output is on if the starting command is
on even when a fault occurs or the MRS signal is on.
When using the RY, RUN and RUN3 signals, assign functions to
Pr. 190 to Pr. 196 (output terminal selection function) referring to the
table below.
Pr. 190 to Pr. 196 Setting
Output
Signal
Positive logic
RY
11
RUN
0
RUN3
45
Related
Refer
Parameters
to Page
125
Pr. 52, Pr. 54,
Pr. 158, Pr. 891 to
154
Pr. 899
Pr. 555 to Pr. 557
259
125
Pr. 503, Pr. 504
258
Pr. 495 to Pr. 497
129
200,
Pr. 121, Pr. 244
254
125
Negative logic
111
100
145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents