Signal
Setting
Name
Pr. 59 = 0 (initial value)
2
RH
Pr. 59 ≠ 0
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Selection of automatic restart after instantaneous power failure,
flying start
6
CS
Electronic bypass function
7
OH
External thermal relay input
8
REX
15 speed selection (combination with three speeds RL, RM, RH)
10
X10
Inverter operation enable signal (FR-HC, MT-HC/FR-CV connection)
11
X11
FR-HC or MT-HC connection, instantaneous power failure detection
12
X12
PU operation external interlock
13
X13
External DC injection brake operation start
14
X14
PID control valid terminal
PU-external operation switchover
16
X16
(external operation when X16 turns on)
Output stop
24
MRS
Electronic bypass function
25
STOP
Start self-holding selection
Forward rotation command
60
STF
(assigned to STF terminal (Pr. 178) only)
Reverse rotation command
61
STR
(assigned to STR terminal (Pr. 179) only)
62
RES
Inverter reset
63
PTC
PTC thermistor input (assigned to AU terminal (Pr. 184) only)
64
X64
PID forward/reverse action switchover
PU-NET operation switchover
65
X65
(PU operation when X65 turns on)
External-NET operation switchover
66
X66
(NET operation when X66 turns on)
Command source switchover
67
X67
(Pr.338 and Pr.339 commands are valid when X67 turns on)
70
X70
DC feeding operation permission
71
X71
DC feeding cancel
72
X72
PID integral value reset
9999
No function
When Pr. 59 Remote function selection ≠ "0", the functions of the RL, RM and RH signals change as listed above.
*1
*2
The OH signal turns on when the relay contact "opens".
REMARKS
⋅ Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
⋅ The priorities of the speed commands are in order of jog > multi-speed setting (RH, RM, RL, REX) > PID (X14).
⋅ When the X10 signal (FR-HC, MT-HC, FR-CV connection - inverter operation enable signal) is not set or when the PU
operation external interlock (X12) signal is not assigned at the Pr. 79 Operation mode selection setting of "7", the MRS signal
shares this function.
⋅ Same signal is used to assign multi-speeds (7 speeds) and remote setting. They cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same time .)
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Also
check that wiring is correct, since the terminal name and the signal function became different. Please make setting after
confirming the function of each terminal.
Function
High-speed operation command
Remote setting (acceleration)
*1
*2
Function assignment of external
terminal and control
Related Parameters
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr.
232 to Pr. 239
Pr. 59
Pr. 44 to Pr. 51
Pr. 267
Pr. 15, Pr. 16
Pr. 57, Pr. 58, Pr.162 to Pr.165,
Pr. 299, Pr. 611
Pr. 57, Pr. 58 Pr. 135 to Pr. 139,
Pr. 159
Pr. 9
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr.232 to Pr.239
Pr. 30
Pr. 30
Pr. 79
Pr. 11, Pr. 12
Pr. 127 to Pr. 134, Pr. 575 to Pr.
577
Pr. 79, Pr. 340
Pr. 17
Pr. 57, Pr. 58, Pr. 135 to Pr. 139,
Pr. 159
Pr. 9
Pr. 127 to Pr. 134
Pr. 79, Pr. 340
Pr. 79, Pr. 340
Pr. 338, Pr. 339
Pr. 30, Pr. 70
Pr. 30, Pr. 70
Pr. 127 to Pr. 134, Pr. 241, Pr.
553, Pr. 554, Pr. 575 to Pr. 577,
C42 to C45
Refer to
Page
88
93
119
161
90
142
237
101
88
108
108
181
106
225
187
118
237
120
120
120
101
225
189
189
190
108
108
225
4
117