Bcc 28 Finish - Bellfires BCC-28 Tall Installation Manual

Close clearance models
Table of Contents

Advertisement

Bellfires® BCC
Finish the BCC
Install
vents
2" (50 mm) to combustible side framing
The BCC 28 is different from most factory-built fireplaces in that the front facewall construction must be entirely
non-combustible. Options include traditional brick or stone facewalls, providing the proper supports and fram-
ing to carry such loads is built. Other possibilities include framing the facewall with metal studding and using
expanded diamond mesh and plaster to achieve the look of finished sheet rock walls. Refer to the manufacturer's
installation guidelines for the metal studding you choose.
It is extremely important that the chase surrounding the BCC be ventilated. Minimum required opening size is 36"
(914 mm) square at top and bottom. The openings may be on the front wall, side walls, or back wall. Two vents are sup -
plied with the BCC 28.
Sheet Metal Emberguard
Ceiling to floor facewall constructed of noncombustible
materials. (All studding metal and all surface materials
noncombustible.) NO Sheetrock or wooden studs.
18" (458 mm) Minimum distance
between opening to wooden mantle
Bellfires® Insulated
Hearth Extension Pad
30
20" (508 mm) non-combustible decorative
hearth material