Wiring

Electrical Installation

Capacitor hazardous voltage! Failure to disconnect power
and discharge capacitors before servicing will result in serious
injury or death.
Disconnect all electric power (including remote disconnects)
before servicing. Perform lockout/tagout procedures to ensure
that power can not be energized. For variable frequency drives,
or other energy storing components that have been furnished
and mounted by either Daikin, or by others, refer to the
specific manufacturer's literature for allowable waiting periods
for discharge of capacitors. Verify capacitors have been
discharged using an appropriate voltmeter.
ADVERTISSEMENT
Voltage de condesateur à risquee de danger! À défaut de
débrancher la puissance électrique et de décharger le
condensateur avant de faire le service, il peut en résulter des
blessures sérieuses et même la mort.
Débranchez toute puissance électrique (incluant les
sectionneurs à distance) avant de faire du service. Assurez-
vous de procéder au cadenassage et à la pose d'avis assurant
que la puissance ne peut être rétablie.
Pour le variateur de fréquence variable ou tout autre
composante pouvant accumuler de l'énergie qui auraient été
fournis et installés par Daikin ou autres, se référer à la
littérature spécifique du manufacturier donnant les périodes
spécifiques d'attente nécessaires pour la décharge du
condensateur. Vérifier que le condensateur est totalement
déchargé avec les voltmètres appropriés.
Use copper conductors only. Failure to use copper
conductors can result in equipment damage.
Utiliser du fil de cuivre seulement. La non utilisation de fil de
cuivre peut causer des dommages à l'équipement.
• Electrical service to each fan must correspond to the rated
voltage on the motor or electrical panel nameplate and
conform to the National Electric Code and local restrictions.
• Connect each fan section metal frame to the building
electrical ground.
• A door electrical interlock is not provided as standard.
• Thermal motor protection is external to the unit.
Locate electrical conduit entrances for units above the bottom
of the unit, high enough to clear components inside, but below
the bottom of the fan motor junction box
Daikin IM 777-7
DANGER
CAUTION
ATTENTION
(Figure
28).
Electrical Installation
Figure 28: Electrical Conduit Location
Fan Motor
Junction Box
The base section of each cabinet has a drip pan installed
below every panel that drains to the outside frame trough. Any
holes cut through the bottom of the unit must also penetrate
the drip pan. If holes are cut in the drip pan, seal them to
prevent moisture leakage.
Chaque cabinet est muni d'une base avec une panne
d'égouttement installée en-dessous de chaque panneau qui
évacuera l'eau vers la gouttière extérieure. Tous les trous
percés au bas de l'unité doivent pénétrer la panne
d'égouttement. S'il y a des trous dans la panne
d'égouttement, les sceller pour empêcher les fuites d'eau.
• When the unit is provided with an external junction box and
variable frequency drive (VFD), the VFD itself will be
mounted on the drive side fan panel inside the fan cabinet.
The external junction box will provide loose wire
connection to the VFD and to the motor. An external
mounted keypad/display control box will be provided and
connected to the VFD for manual adjustment of the VFD.
• When not being serviced, close and secure electrical panel
doors to prevent accidental contact with live parts and
prevent ingress of moisture and airborne contaminants.
• For instances where multiple motors are being driven by a
single VFD, be sure to set up the VFD and size the wiring
according to the power requirements of all motors that are
being driven by that VFD.
Conduit Entrance
(typical)
CAUTION
ATTENTION
17