Figure 31: Wheel-to-Inlet Funnel Relationship—13 to 36
Belt-Drive Plenum Fans
Cross Section Reference
B
FROM FUNNEL END TO
FANWHEEL OPENING END
A
C
Table 8: Wheel-to-Inlet Funnel Relationship—13 to 36 Belt-
Drive Plenum Fan
Wheel-Funnel Parameters
Size
A
13
0.25
15
0.25
16
0.25
18
0.38
20
0.42
22
0.45
24
0.51
27
0.55
30
0.62
33
0.55
36
0.63
Figure 33: Fan Wheel Rotation
Daikin IM 777-7
EQUALLY SPACED
AROUND DIAMETER
B
C
0.91
3.50
0.91
3.50
0.91
3.50
0.86
3.88
1.11
3.88
1.11
3.88
1.11
3.88
1.36
4.50
1.36
4.50
1.50
5.00
1.50
5.00
Operation Guidelines
Figure 32: Wheel-to-Inlet Funnel Relationship—40 to 60
Belt-Drive Plenum Fans
Cross Section Reference
FUNNEL END TO FAN
WHEEL OPENING
C
Table 9: Wheel-to-Inlet Funnel Relationship—40 to 60 Belt-
Drive Plenum Fan
Wheel-Funnel Parameters
Size
A
40
0.82
44
0.91
49
1.00
54
1.10
60
1.23
A
EQUALLY
SPACED AROUND
B
DIAMETER
B
2.00
2.25
2.50
2.50
3.00
C
4.88
5.50
5.50
5.50
5.50
21