Special System Timers; Waterflow Circuits Operation; Disable/Enable Operation; Style 6 Operation - Notifier AFP-200 Installation Manual

Analog fire panel
Hide thumbs Also See for AFP-200:
Table of Contents

Advertisement

Operation

4.9 Read Status

118
Technical Manuals Online! - http://www.tech-man.com

4.8.4 Special System Timers

The control panel can operate with special system timers: Silence Inhibit, Auto Silence,
and Alarm Verification. Table 40 contains descriptions of how each timer works.
Timer
Duration
Silence Inhibit
0-300 seconds
Auto Silence
600-900
seconds(0=no timer
selected)
Alarm
0-30 seconds
Verification
Table 40 Special System Timers

4.8.5 Waterflow Circuits Operation

If an alarm exists from a monitor module point that has a Waterflow type code, the
key will not function.
ALARM SILENCE

4.8.6 Disable/Enable Operation

Disabled input points do not cause an alarm or any Control-by-Event activity. The
control panel does the following:
Holds all disabled output points in the off-state
Handles all disabled points as troubles, but displays DISABL in the status banner.

4.8.7 Style 6 Operation

The control panel will detect a trouble in an SLC wired and programmed for Style 6 or
Style 7 and drive both ends of the line to maintain communication over the SLC. The
trouble latches and displays on the control panel as a Style 6 trouble type until you press
the
key on the control panel. Style 7 requires use of ISO-X modules.
SYSTEM RESET

4.9.1 Overview

Read Status functions do not require a password. The control panel continues to provide
fire protection while in Read Status. You can enter Read Status while in Fire Alarm or
Trouble mode. If a new alarm or trouble occurs during Read Status functions, the
control panel automatically exits Read Status.
If selected
Starts at first alarm and restarts with each new
alarm. Disables the
ALARM SILENCE
Automatically shuts off outputs selected as
silenceable after the programmed time elapses.
To restart the timer, press the
DRILL
The control panel ignores an FSI or FSP smoke
detector for the Alarm Verification time. If another
point alarm occurs during the Alarm Verification
time, the control panel dumps the timer and
activates the alarm. If a time-out and an alarm
exist, the initiating device CBE executes all
standard functions. If at time-out an alarm no
longer exists in the alarm initiating device, the
control panel increments a verification counter
(1-99) for the device and returns to normal
operation.
AFP-200 PN 15511:H2 10/14/2002
Read Status
key.
key.