Dip Switch Configuration - RAMSET RAM 100 Instruction Manual

Hide thumbs Also See for RAM 100:
Table of Contents

Advertisement

RAMSET
DIP SWITCH "A"
Dip Switch "A" 1, 2 & 3;
AUTOMATIC TIMER TO CLOSE GATE
'0' is "OFF"
'1' is "ON"
Switch
1
2
3
Gate Open Duration:
1
1
1
60 seconds
1
1
0
45 seconds
1
0
1
30 seconds
1
0
0
15 seconds
0
1
1
10 seconds
0
1
0
05 seconds
0
0
1
00 seconds
0
0
0
Disabled - command required to close
Dip Switch "A" 4 - 1/2 hP ERD
Dip switch A4 works with Dip switch B8
DIP A4
B8
Sensitivity
OFF
OFF
Most Sensitive
ON
OFF
1/2 Hp — Medium Sensitivity
OFF
ON
3/4 Hp — Medium Sensitivity
ON
ON
Least Sensitive
DIP SWITCH "B"
Dip Switch "B" 1; Not in use at this time.
Leave in the 'Off' position.
12

DIP SWITCh CONFIGURATION

Dip Switch "B" 2; "PRE WARN"
Used with jP2 "Relay Connections": pins 7 & 8.
Triggers a relay, for an alarm or light (not included), for 3 sec-
onds before the gate will move in any direction.
Dip Switch "B" 3; "CONSTANT WARN"
Used with jP2 "Relay Connections": pins 7 & 8.
Triggers a relay, for an alarm or light (not included), to be ac-
tive anytime the gate is in motion.
Dip Switch "B" 4,5,6 & 7; Not in use at this time.
Dip Switch "B" 8 - 3/4 hP ERD
Dip switch B8 works with Dip switch A4
DIP A4
www.ramsetinc.com
"Intelligate" Control Board
Sw.
Function:
ON
Triggers the relay on jP2 pins 7 & 8 for 3 seconds.
OFF Regular working conditions
Sw.
Function:
Triggers the relay on jP2 pins 7 & 8 while the gate
ON
is moving
OFF Regular working conditions
Leave in the 'Off' position.
B8
Sensitivity
OFF
OFF
Most Sensitive
ON
OFF
1/2 Hp — Medium Sensitivity
OFF
ON
3/4 Hp — Medium Sensitivity
ON
ON
Least Sensitive
Figure 17